Example 2 – Writing data to the network

The DeviceLogix program controls an Analog Output value which is written to
DLX Real OutSP1.

DLX Real OutSP1 can now be used as a Hardware Analog Output and used
directly with a Function Block (a DeviceLogix Datalink is not required).

Program Examples

Example 1: Selector Switch Operation

This example demonstrates how a selector switch operation similar to the feature
in the PowerFlex 700S can be achieved through the embedded DeviceLogix in
the PowerFlex 750-Series drive. A selector switch is simulated in the drive using a
combination of inputs to produce multiple outputs. Digital inputs in the drive
are used to output configurable multiple preset speeds (75 Hz, 85Hz, 95Hz, and
105Hz) to P571 [Preset Speed 1]. It is assumed that the 750-Series drive has an I/
O module that is installed in Port 4.

The following truth table represents the inputs and outputs for a 4 position
selector switch.

The Logic Map offers a high level explanation of how the above outputs are
achieved.

Drive

Datalink

Value

753

Port 0 P905 [Data Out A1]

Port 14: DLX Real OutSP1

755

Port 13 P17 [DL To Net 01]

Inputs

Outputs

Input 1

Input 2

Binary Output

Selector Switch
Output

0

0

0

Output A

0

1

1

Output B

1

0

2

Output C

1

1

3

Output D