Dual Incremental Encoder
Faults and Alarms

The table below contains a list of encoder-specific faults and alarms, the type of
fault or alarm, the action taken when the drive faults, the parameter used to
configure the fault or alarm (if applicable), and a description and action (where
applicable).

Table 22 - Dual Incremental Encoder Fault and Alarm Types, Descriptions and Actions

Event
No.

(1)

Fault/Alarm Text

Type

Fault
Action

Configuration
Parameter

Auto
Reset

Description/Action(s)

xx000

Enc0 Open Wire

Configurable

P3
[Enc 0 FB Lss Cfg]

The dual encoder module has detected an encoder 0 input signal (A, B,
or Z) in the same state as its complement (A Not, B Not, or Z Not). For
open wire detection to work, the encoder signals must be differential
(not single ended). The Z channel is only checked when enabled. See P1
[Enc 0 Cfg].

xx001

Enc0 Phase Loss

Configurable

P3
[Enc 0 FB Lss Cfg]

More than 30 encoder 0 phase loss (open wire) events have occurred
over an 8 millisecond time period. The same restrictions as for Enc0
Open Wire detection apply.

xx002

Enc0 Quad Loss

Configurable

P3
[Enc 0 FB Lss Cfg]

Encoder 0 Quadrature loss events occur when simultaneous edge
transitions occur on both the A and B channels of encoder 0. This fault
will occur when more than 10 quad loss events over a 10 millisecond
time period are detected. Only valid when both A and B channels are
used (not Bit 1 “A Chan Only”) in P1 [Enc 0 Cfg].

xx030

Enc1 Open Wire

Configurable

P13
[Enc 1 FB Lss Cfg]

The dual encoder module has detected an encoder 1 input signal (A, B,
or Z) in the same state as its complement (A Not, B Not, or Z Not). For
open wire detection to work, the encoder signals must be differential
(not single ended). The Z channel is only checked when enabled. See
P11 [Enc 1 Cfg].

xx031

Enc1 Phase Loss

Configurable

P13
[Enc 1 FB Lss Cfg]

More than 30 encoder 1 phase loss (open wire) events have occurred
over an 8 millisecond time period. The same restrictions as for Enc1
Open Wire detection apply.

xx032

Enc1 Quad Loss

Configurable

P13
[Enc 1 FB Lss Cfg]

Encoder 1 Quadrature loss events occur when simultaneous edge
transitions occur on both the A and B channels of encoder 1. This fault
will occur when more than 10 quad loss events over a 10 millisecond
time period are detected. Only valid when both A and B channels are
used (not Bit 1 “A Chan Only”) in P11 [Enc 1 Cfg].

xx058

Module Defaulted

Fault

Coast

Module was commanded to write default values.

(1)

xx

indicates the port number. Refer to

Fault and Alarm Display Codes on page 312

for an explanation.