HIM Indication

Fault Display Screen

The pop-up Fault Display screen automatically appears when a fault condition
for the Host Drive or any connected peripheral is detected. The pop-up Fault
Display screen flashes to alert that a fault condition exists. This screen displays
the:

Fault Code number (See

Fault and Alarm Display Codes on page 312

.)

Fault description

Elapsed time (in hh:mm:ss format) from fault detection

Figure 4 - Pop-Up/Flashing Fault Display Screen

Soft Key Functions

Single Function Key

Manually Clearing Faults

Label

Name

Description

ESC

Escape

Reverts back to the previous screen without clearing the fault.

CLR

Clear

Removes the pop-up Fault Display screen from the display and clears
the fault.

Key

Name

Description

Stop

Removes the pop-up Fault Display screen from the display and clears the
fault.

Stopped

0.00 Hz

AUTO

Fault Code 81

Port 1 DPI Loss

Elapsed Time 01:26:37

ESC

F

CLR

– – FAULTED – –

Step

Key(s)

1. Press the “Clear” soft key to acknowledge the fault. The fault information will be removed so that

you can use the HIM.

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.

3. After corrective action has been taken, clear the fault by one of these methods:

Press Stop (if running the drive will stop)
Cycle drive power
Select the “Clear” soft key on the HIM Diagnostic folder Faults menu.