Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 265

Advertising
background image

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

265

Embedded Feature and Option Module Parameters

Chapter 5

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

22

-Serie

s I/O

Predi

ct

iv

e M

ain

99

PredMaint Sts
Predictive Maintenance Status

RO

16-bit
Integer

Status of relay's predictive maintenance.

(1) Bit 1= “Relay Out 0” for 22-Series I/O Module models 20-750-2262C-2R and 20-750-2262D-2R

100

RO0 Load Type
Relay Output 0 Load Type
Sets the type of load that will be applied to the relay. Must be properly set for the
Predictive Maintenance function to predict the relay life.

Default:
Options:

1 = “DC Inductive”
0 = “DC Resistive”
1 = “DC Inductive”
2 = “AC Resistive”
3 = “AC Inductive”

RW 32-bit

Integer

101

RO0 Load Amps
Relay Output 0 Load Amps
Load current that will be applied to the relay contacts. Must be properly set for the
Predictive Maintenance function to approximate the relay life.

Units:
Default:
Min/Max:

Amps
2.000
0.000 / 2.000

RW Real

102

RO0 TotalLife
Relay Output 0 Total Life
Total life cycles of the relay based on programmed load type and amps.

Units:
Default:
Min/Max:

Cycl
0
0 / 2147483647

RO

32-bit
Integer

103

RO0 ElapsedLife
Relay Output 0 Elapsed Life
Non-resettable, total accumulated cycles of the relay.

Units:
Default:
Min/Max:

Cycl
0
0 / 2147483647

RO

32-bit
Integer

104

RO0 RemainLife
Relay Output 0 Remaining Life
The difference between the Total Life and the Elapsed Life.

Units:
Default:
Min/Max:

Cycl
0
–/+2147483647

RO

32-bit
Integer

105

RO0 LifeEvntLvl
Relay Output 0 Life Event Level
Sets the percentage of relay life cycles before action is taken.

Units:
Default:
Min/Max:

%
80.000
0.000 / 100.000

RW Real

106

RO0 LifeEvntActn
Relay Output 0 Life Event Action
Sets the action that will be taken when the percentage of relay life cycles has been
reached.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.

Default:
Options:

1 = “Alarm”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop”
5 = “Flt CL Stop”

RW 32-bit

Integer

Options

Mast

er

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

la

y Out

0

(1

)

Re

la

y Out

0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True