Rockwell Automation Publication 750-PM001J-EN-P - October 2014

507

Integrated Motion on EtherNet/IP

Appendix E

Feedback Configuration
Options

The following feedback module combinations are supported.

An invalid hardware configuration results in a Module Fault: (Code 16#0010)
Mode or state of module does not allow object to perform requested service.

Considerations for Using Position Feedback Devices on the PowerFlex
755 in the Integrated Motion on EtherNet/IP Context

The PowerFlex 755 connects to position feedback devices (encoders) using one
or more feedback option modules that are placed in the PowerFlex 755 control
pod.

There are currently three supported types of feedback modules: 20-750-ENC-1,
20-750-DENC-1, and 20-750-UFB-1.

The 20-750-DENC-1 and 20-750-UFB-1 each contain two “hardware feedback
channels”, which means up to two encoders can be connected to each module.
The 20-750-ENC-1 only contains one hardware feedback channel.

Option

Supported Module

Catalog Number

Valid Ports

Two Feedback Options

Single Incremental Encoder

20-750-ENC-1

4…8

Dual Incremental Encoder

20-750-DENC-1

4…8

Universal Feedback

20-750-UFB-1

4…6

Two Feedback Options and
One Safe Torque Off
Option

Single Incremental Encoder

20-750-ENC-1

4 and 5

Dual Incremental Encoder

20-750-DENC-1

4 and 5

Universal Feedback

20-750-UFB-1

4 and 5

Safe Torque Off

20-750-S

6

Two Feedback Options and
One Safe-Speed Monitor
Option

(1)

(1) The Safe Speed Monitor option module must be used with the 20-750-DENC-1 Dual Incremental Encoder module or the 20-750-

UFB-1 Universal Feedback module.

Single Incremental Encoder

20-750-ENC-1

4 and 5

Dual Incremental Encoder

20-750-DENC-1

4 and 5

Universal Feedback

20-750-UFB-1

4 and 5

Safe Speed Monitor

20-750-S1

6

IMPORTANT

Single and dual incremental feedback options, 20-750-ENC-1 and 20-750-
DENC-1, cannot use registration inputs. Use the Universal Feedback option 20-
750-UFB-1 if registration homing inputs are needed.