Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 263

Advertising
background image

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

263

Embedded Feature and Option Module Parameters

Chapter 5

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

22

-S

er

ies I/O

An

al

og O

u

tpu

ts

70

Anlg Out Type
Analog Output Type

RW 16-bit

Integer

Select the analog output mode for each analog output.

71

Anlg Out Abs
Analog Output Absolute

RW 16-bit

Integer

Selects whether the signed value or absolute value of a parameter is used before being scaled to drive the analog output.

75

Anlg Out0 Sel
Analog Output 0 Select
Selects the source for the analog output.

Default:
Min/Max:

3
0 / 159999

RW 32-bit

Integer

76

Anlg Out0 Stpt
Analog Output 0 Setpoint
A possible source for an analog output. Can be used to control an analog output from a
communication device using a DataLink. Not affected by analog output scaling.

Units:

Default:

Min/Max:

Volt
mA
10.000 Volts
20.000 mA
–/+10.000 Volts
0.000 / 20.000 mA

RW Real

77

Anlg Out0 Data
Analog Output 0 Data
Displays the value of the source selected by P75 [Anlg Out0 Sel].

Default:
Min/Max:

0
–/+40000.000

RO

Real

78

Anlg Out0 DataHi
Analog Output 0 Data High
Sets the high value for the data range of analog out scale.

Units:
Default:
Min/Max:

pu
1
–/+40000.000

RW Real

79

Anlg Out0 DataLo
Analog Output 0 Data Low
Sets the low value for the data range of analog out scale.

Default:
Min/Max:

1
–/+40000.000

RW Real

80

Anlg Out0 Hi
Analog Output 0 High
Sets the high value for the analog output value when the data value is at its maximum.

Units:

Default:

Min/Max:

Volt
mA
10.000 Volts
20.000 mA
–/+10.000 Volts
0.000 / 20.000 mA

RW Real

81

Anlg Out0 Lo
Analog Output 0 Low
Sets the low value for the analog output value when the data value is at its minimum.

Units:

Default:

Min/Max:

Volt
mA
0.000 Volts
0.000 mA
–/+10.000 Volts
0.000 / 20.000 mA

RW Real

Options

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

An

al

og

1

An

al

og

0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Voltage Mode
1 = Current Mode

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Analog 1

Analog 0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True