Chapter 3

Drive Port 0 Parameters

APPLIC

AT

ION

S

Proces

s P

ID

1084

PID LP Filter BW
PID Low Pass Filter Bandwidth
Sets the level of filtering applied to the error signal. Zero will disable this filter.

Units:
Default:
Min/Max:

R/S
0.00
0.00 / 100.00

RW Real

1085

PID Preload
PID Preload
Sets the value used to preload PID Integrator when PID is enabled and P1065 [PID Cfg]
Bit 0 “Preload Int” is set to 1.

Units:
Default:
Min/Max:

%
0.00
–/+100.00

RW Real

1086

PID Prop Gain
PID Proportional Gain
Sets the value for the PID proportional component.
PID ErrorMeter x PID Prop Gain = PID Output

Default:
Min/Max:

1.00
0.00 / 100.00

RW Real

1087

PID Int Time
PID Integral Time
Time required for the integral component to reach 100% of P1092 [PID Error Meter]. Not
used when P1066 [PID Control] Bit 1 “PID Hold” = 1 (enabled).

Units:
Default:
Min/Max:

Secs
1.00
0.00 / 100.00

RW Real

1088

PID Deriv Time
PID Derivative Time
Refer to formula below:

KD = P1088
d

PI Error

= Error - Last Error

d

t

= Interrupt Time

A setting of zero disables this parameter.

Units:
Default:
Min/Max:

Secs
0.00
0.00 / 100.00

RW Real

1089

PID Status
PID Status

RO

16-bit
Integer

Status of the Process PI regulator.

Bit 0 “PID Enable” – PID controller is enabled.
Bit 1 “PID Hold” – Hold PID integrator.
Bit 2 “PID Reset” – Reset PID integrator.
Bit 3 “PID In Limit” – PID in limit.

1090

PID Ref Meter
PID Reference Meter
Present value of the PI reference signal.

Units:
Default:
Min/Max:

%
0.00
–/+100.00

RO

Real

1091

PID Fdbk Meter
PID Feedback Meter
Present value of the PI feedback signal.

Units:
Default:
Min/Max:

%
0.00
–/+100.00

RO

Real

1092

PID Error Meter
PID Error Meter
Present value of the PI error.

Units:
Default:
Min/Max:

%
0.00
–/+200.00

RO

Real

1093

PID Output Meter
PID Output Meter
Present value of the PI output.

Units:
Default:
Min/Max:

%
0.00
–/+800.00

RO

Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

d

PI Error

(%)

d

t

(Sec)

PID

Out

= KD (Sec) x

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

PID In Limit

PID Re

set

PID Hold

PID En

ab

led

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True