Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 80

Advertising
background image

80

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 3

Drive Port 0 Parameters

FEEDBA

CK &

I/O

An

al

og In

pu

ts

256

Anlg In Sqrt

Analog Input Square Root

RO

16-bit
Integer

Enables/disables the square root function for each input.

257

Anlg In Loss Sts

Analog Input Loss Status

RO

16-bit
Integer

Status of the analog input loss.

260

Anlg In0 Value

Analog Input 0 Value
Value of the Analog input after filter, square root, and loss action.

Units:

Default:

Min/Max:

Volt
mA
0.000 Volts
0.000 mA
–/+10.000 Volts
0.000 / 20.000 mA

RO

Real

261

Anlg In0 Hi

Analog Input 0 High
Sets the highest input value to the analog input scaling block.

Units:

Default:

Min/Max:

Volt
mA
0.000 Volts
0.000 mA
–/+10.000 Volts
0.000 / 20.000 mA

RW Real

262

Anlg In0 Lo

Analog Input 0 Low
Sets the lowest input value to the analog input scaling block.

Units

Default:

Min/Max:

Volts
mA
0.000 Volts
0.000 mA
–/+10.000 Volts
0.000 / 20.000 mA

RW Real

263

Anlg In0 LssActn

Analog Input 0 Loss Action
Selects drive action when an analog signal loss is detected. Signal loss is defined as an
analog signal less than 1V or 2mA. The signal loss event ends and normal operation
resumes when the input signal level is greater than or equal to 1.5V or 3mA.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.
“Hold Input” (6) – Holds input at last value.
“Set Input Lo” (7) – Sets input to P262 [Anlg In0 Lo].
“Set Input Hi” (8) – Sets input to P261 [Anlg In0 Hi].

Default:
Options:

0 = “Ignore”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop”
5 = “Flt CL Stop”
6 = “Hold Input”
7 = “Set Input Lo”
8 = “Set Input Hi”

RW 32-bit

Integer

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

753

Options

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

An

al

og

0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Square Root Disabled
1 = Square Root Enabled

753

Options

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Lo

ss

0

Res

er

ved

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Loss not Present
1 = Loss Present

753

753

753

753

Advertising