Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 317

Advertising
background image

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

317

Troubleshooting

Chapter 6

102

NVS Not Blank

Resettable
Fault

Coast

Internal data error.

103

PwrDn NVS Incomp

Resettable
Fault

Coast

Internal data error.

104

Pwr Brd Checksum

Non-Reset
Fault

The checksum read from the non-volatile storage does not match the
checksum calculated. Data set to default value.

106

Incompat MCB-PB

Non-Reset
Fault

Coast

The main control board did not recognize the power structure. Flash
with newer Application version.

107

Replaced MCB-PB

Resettable
Fault

Coast

The main control board was moved to a different power structure. Data
set to default values.

108

Anlg Cal Chksum

Non-Reset
Fault

Coast

The checksum read from the analog calibration data does not match the
checksum calculated. Replace main control board.

110

Ivld Pwr Bd Data

Non-Reset
Fault

Coast

Power structure data invalid.
Verify ribbon cable connection between the main control board and

the power interface board.

Replace power interface board.

111

PwrBd Invalid ID

Non-Reset
Fault

Coast

Power structure ID invalid.
Verify ribbon cable connection between the main control board and

the power interface board.

Replace power interface board.

112

PwrBd App MinVer

Resettable
Fault

Coast

Power structure needs newer Application version. Flash with newer
Application version.

113

Tracking DataErr

Resettable
Fault

Coast

Internal data error.

115

PwrDn Table Full

Resettable
Fault

Coast

Internal data error.

116

PwrDnEntry2Large

Resettable
Fault

Coast

Internal data error.

117

PwrDn Data Chksm

Resettable
Fault

Coast

Internal data error.

118

PwrBd PwrDn Chks

Resettable
Fault

Coast

Internal data error.

124

App ID Changed

Resettable
Fault

Coast

Application Firmware changed. Verify Application version.

125

Using Backup App

Resettable
Fault

Coast

Application did not flash correctly. Reflash.

134

Start On PowerUp

Alarm 1

When P345 [Start At PowerUp] is enabled, an alarm will be set for the
time programmed in P346 [PowerUp Delay].

137

Ext Prechrg Err

Configurable

323

[Prchrg Err Cfg]

The seal contact on the external precharge contactor has opened (as
signalled by P190 [DI Prchrg Seal]) while the drive was running (PWM
was active).

138

Precharge Open

Resettable
Fault

Coast

321

[Prchrg Control]

190

[DI Prchrg Seal]

189

[DI Precharge]

The internal precharge was commanded to open while the drive was
running (PWM was active). The internal fault latch will be automatically
cleared when PWM is disabled.

141

Autn Enc Angle

Resettable
Fault

Coast

P78 [Encdrlss AngComp] is out of range.

142

Autn Spd Rstrct

Resettable
Fault

Coast

Frequency limit settings are preventing the drive from reaching a
suitable speed during an Inertia Tune test.

143

Autotune CurReg

Resettable
Fault

Coast

Calculated values for P96 [VCL Cur Reg Kp] and/or P97 [VCL Cur Reg Ki]
are out of range.

144

Autotune Inertia

Resettable
Fault

Coast

Results from the Inertia Tune test out of range for P76 [Total Inertia].

145

Autotune Travel

Resettable
Fault

Coast

When P77 [Inertia Test Lmt] is set, the Inertia Tune test was prevented
from reaching a suitable speed to run the test.

Event
No.

Fault/Alarm Text

Type

Fault
Action

Configuration
Parameter

Auto
Reset

Description/Action(s)