Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 72

Advertising
background image

72

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 3

Drive Port 0 Parameters

FEEDBA

CK &

I/O

Digi

n F

u

n

cti

ons

165

DI Run Reverse
Digital Input Run Reverse
Assigns a digital input used to run the drive (2 wire control) and command reverse
direction.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

166

DI Jog 1
Digital Input Jog 1
Assigns a digital input used to jog the drive at the speed of P556 [Jog Speed 1].

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

167

DI Jog 1 Forward
Digital Input Jog 1 Forward
Assigns a digital input used to jog the drive in the forward direction at the speed of P556
[Jog Speed 1].

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

168

DI Jog 1 Reverse
Digital Input Jog 1 Reverse
Assigns a digital input used to jog the drive in the reverse direction at the speed of P556
[Jog Speed 1].

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

169

DI Jog 2
Digital Input Jog 2
Assigns a digital input used to jog the drive at the speed of P557 [Jog Speed 2].

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

170

DI Jog 2 Forward
Digital Input Jog 2 Forward
Assigns a digital input used to jog the drive in the forward direction at the speed of P557
[Jog Speed 2].

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

171

DI Jog 2 Reverse
Digital Input Jog 2 Reverse
Assigns a digital input used to jog the drive in the reverse direction at the speed of P557
[Jog Speed 2].

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

172

DI Manual Ctrl
Digital Input Manual Control
Assigns a digital input used to command manual control. Start, jog, and direction are
under the digital input’s exclusive control. P563 [DI ManRef Sel] is the source of the
speed reference unless overwritten by P328 [Alt Man Ref Sel].

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

173
174
175

DI Speed Sel 0
DI Speed Sel 1
DI Speed Sel 2
Digital Input Speed Select n
Assigns digital inputs used to select between speed references as follows:

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

Input Status (1 = Input Actuated)

Auto Reference Source
(Parameter)

DI Speed Sel 2

DI Speed Sel 1

DI Speed Sel 0

0

0

0

Reference A (P545)

0

0

1

Reference A (P545)

0

1

0

Reference B (P550)

0

1

1

Preset Speed 3 (P573)

1

0

0

Preset Speed 4 (P574)

1

0

1

Preset Speed 5 (P575)

1

1

0

Preset Speed 6 (P576)

1

1

1

Preset Speed 7 (P577)

Advertising