Drive (port 0) monitor file – Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 3

Drive Port 0 Parameters

Drive (Port 0) Monitor File

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

MON

IT

O

R

Meterin

g

1

Output Frequency
Output Frequency
Output frequency present at terminals T1, T2, and T3 (U, V & W)

Units:
Default:
Min/Max:

Hz
0.00
–/+650.00

RO

Real

2

Commanded SpdRef
Commanded Speed Reference
Value of the active Speed/Frequency Reference. Displayed in Hz or RPM, depending on
the value of P300 [Speed Units].

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz] x 8
–/+P28 [Motor NP RPM] x 8

RO

Real

3

Mtr Vel Fdbk
Motor Velocity Feedback
Estimated or actual motor speed, with feedback. Displayed in Hz or RPM, depending
on the value of P300 [Speed Units].

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz] x 8
–/+P28 [Motor NP RPM] x 8

RO

Real

4

Commanded Trq
Commanded Torque
External torque regulation reference. Summation of Torque A Select Reference and
Torque B Select Reference. Percent of motor rated torque. See

Table 17 on page 381

.

Units:
Default:
Min/Max:

%
0.00
–/+800.00

RO

Real

5

Torque Cur Fdbk
Torque Current Feedback
Based on the motor, the amount of current that is in phase with the fundamental
voltage component.

Units:
Default:
Min/Max:

Amps
Based on Drive Rating
–/+P21 [Rated Amps] x 2

RO

Real

6

Flux Cur Fdbk
Flux Current Feedback
Amount of current that is out of phase with the fundamental voltage component.

Units:
Default:
Min/Max:

Amps
Based on Drive Rating
–/+P21 [Rated Amps] x 2

RO

Real

7

Output Current
Output Current
The total output current present at terminals T1, T2, and T3 (U, V & W).

Units:
Default:
Min/Max:

Amps
Based on Drive Rating
0.00 / P21 [Rated Amps] x 2

RO

Real

8

Output Voltage
Output Voltage
Output voltage present at terminals T1, T2, and T3 (U, V & W).

Units:
Default:
Min/Max:

V AC
Based on Drive Rating
0.00 / P20 [Rated Volts] x 1.15

RO

Real

9

Output Power
Output Power
Output power present at terminals T1, T2, and T3 (U, V & W).

Units:
Default:
Min/Max:

kW
0.00
0.00 / 3000.00

RO

Real

10

Output Powr Fctr
Output Power Factor
Output power factor.

Default:
Min/Max:

0.00
0.00 / 1.00

RO

Real

11

DC Bus Volts
Direct Current Bus Volts
DC bus voltage.

Units:
Default:
Min/Max:

V DC
Based on Drive Rating
0.00 / P20 [Rated Volts] x 2

RO

Real

12

DC Bus Memory
Direct Current Bus Memory
A six-minute average of P11 [DC Bus Volts] used to estimate the DC equivalent of the
input voltage. Automatically initialized upon power-up or precharge, continually
updated during normal operation, and is used to trigger a power loss condition. Use
P464 [DC Bus Mem Reset] to reset this parameter.

Units:
Default:
Min/Max:

V DC
Based on Drive Rating
0.00 / P20 [Rated Volts] x 2

RO

Real

13

Elapsed MWH
Elapsed Megawatt Hour
Accumulated output energy of the drive. Use P336 [Reset Meters] to reset this
parameter.

Units:
Default:
Min/Max:

MWh
0.000
0.000 / 4294967296.000

RO

Real