Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Appendix B

Application Notes

6.

Set speed reference.

Program preset speeds according to Speed Select inputs that are used.

7.

Run crane with crane control unit.

Verify speed references by checking P930 [Speed Ref Source].

8.

Set speed loop tuning.

P645 [Speed Reg Kp] = P636 [Speed Reg BW] x P76 [Total Inertia] = BW x J (Inertia)

Input Status (1 = Input Actuated)

Auto Reference
Source

DI Speed Sel 2

DI Speed Sel 1

DI Speed Sel 0

0

0

0

Reference A

0

0

1

Reference A

0

1

0

Reference B

0

1

1

Preset Speed 3

1

0

0

Preset Speed 4

1

0

1

Preset Speed 5

1

1

0

Preset Speed 6

1

1

1

Preset Speed 7

I/O Module Parameter (Port X)

Setting

P10 [RO0 Sel]

Port 0, P935 [Drive Status 1], Bit 16 “Running”

Drive Parameter

Setting

P636 [Speed Reg BW]

20 R/S
Defines the reactivity of the speed regulator. This parameter is
used to calculate Kp and Ki gains.

P76 [Total Inertia]

1.5 Secs
This value can be increased or decreased depending on Speed
regulator response.