Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 334

Advertising
background image

334

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 6

Troubleshooting

11113
11213
11313

C1 TVSS Blown
C2 TVSS Blown
C3 TVSS Blown

Alarm 1

The MOV block is reporting that the transient voltage suppression
system (TVSS) has blown.

Check the MOV wiring harness for loose connections and/or damage

and replace if necessary.

Replace the MOV block.
If the MOV block is not blown and the wiring harness is properly

connected and not damaged, replace the converter gate firing board.

11114
11214
11314

C1 Blower Speed
C2 Blower Speed
C3 Blower Speed

Alarm 1

The converter cooling fan is running below normal operating speed.

Check for debris in the fan. If necessary, clean the fan and housing.
Check for noise at the fan, indicating motor bearing failure.
Verify that the fan power and feedback connections are not loose or

disconnected.

Replace the fan, if necessary.

11115
11215
11315

C1 Line Dip
C2 Line Dip
C3 Line Dip

Alarm 1

Y

The bus voltage has fallen below the value specified in P451 [Pwr Loss A
Level] or P454 [Pwr Loss B Level] (port 0) minus 20 volts. Until the
converter has established communications with the main control board,
this value defaults to 180V below the converter bus memory. The
converter stops firing the SCRs until the nominal value of the DC bus
voltage for the present AC line voltage is within 60 volts of P12 [DC Bus
Memory] (port 0). If the line dip condition persists for more than 60
seconds the alarm becomes a fault.

Verify the power wiring connections.
Compare the actual DC bus voltage to the value displayed in [Cn DC

Bus Volt]. If the values are different, replace the converter gate firing
board.

Resettable
Fault

Coast

11116
11216
11316

C1 Minimum Line
C2 Minimum Line
C3 Minimum Line

Alarm 1

The AC line voltage is less than 280V (for a 400V class drive) / 400V (for a
600V class drive).

The AC line voltage must exceed 320V / 440V in order to recover from

this alarm.

11117
11217
11317

C1 Line Freq
C2 Line Freq
C3 Line Freq

Alarm 1

The measured line frequency is out of the range (below 40 Hz, or above
65 Hz). This alarm becomes a fault if the condition persists for more than
30 seconds.

Check the incoming power line frequency.
Check the wiring harness to the converter gate firing board for loose

connections and/or damage and replace if necessary.

If the wiring harness is properly connected and not damaged,

replace the converter gate firing board.

Resettable
Fault

Coast

11118
11218
11318

C1 Single Phase
C2 Single Phase
C3 Single Phase

Alarm 1

The converter was intentionally powered up in single-phase mode with
only AC phase L1-L2 present. Intentional single-phase mode is only
detected at the initial application of AC line voltage. Application of 3-
phase voltage after the converter has entered single-phase mode will
result in the single phase alarm becoming a fault.

Verify that only a single phase is applied to a drive in single-phase

mode.

Resettable
Fault

Coast

11134
11234
11334

C1 Overcurrent
C2 Overcurrent
C3 Overcurrent

Resettable
Fault

Coast

The peak AC input current has exceeded 3000A for five line cycles.

Verify that the current transducers are connected.
Check the wiring harness to the converter gate firing board for loose

connections or damage and replace if necessary.

If the current transducers are properly connect and the wiring

harness for the gate firing board is OK, replace the converter gate
firing board.

Check for an open SCR or DC bus short.

Event
No.

Fault/Alarm Text

Type

Fault
Action

Configuration
Parameter

Auto
Reset

Description/Action(s)

Advertising