Rockwell Automation Publication 750-PM001J-EN-P - October 2014

65

Drive Port 0 Parameters

Chapter 3

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

MOT

O

R

CONTRO

L

Ve

ct

or

R

eg

ul

at

or

95

VCL Cur Reg BW
Vector Closed Loop Current Regulator Bandwidth
Sets the bandwidth of the current regulator by automatically adjusting the gains (P96
and P97) based on motor autotune results. When the value of bandwidth is zero
(default) the current regulator gains can be manually adjusted. The default values for
P95, P96, and P97 typically provide excellent performance, and do not normally need to
be adjusted.

Units:
Default:
Min/Max:

R/S
0.0
0.0 / 9999.0

RW Real

96

VCL Cur Reg Kp
Vector Closed Loop Current Regulator Proportional Gain
Proportional gain of the current regulator. Can be adjusted when P95 is set to zero. The
default values for P95, P96, and P97 typically provide excellent performance, and do not
normally need to be adjusted.

Default:
Min/Max:

1250.0
0.0 / 50000.0

0.0 / 10000.0

RW Real

97

VCL Cur Reg Ki
Vector Closed Loop Current Regulator Integral Gain
Integral gain of the current regulator. Can be adjusted when P95 is set to zero. The
default values for P95, P96, and P97 typically provide excellent performance, and do not
normally need to be adjusted.

Default:
Min/Max:

60.0
0.0 / 50000.0

0.0 / 10000.0

RW Real

98

VEncdls FReg Kp
Encoderless Vector Frequency Regulator Proportional Gain
Represents electrical angle compensation dependent on motor cable and PWM
Frequency. Determined during autotuning when P35 [Motor Ctrl Mode] is set to one of
the FV modes without speed feedback.

Units:
Default:
Min/Max:

Hz/A
524.0
0.0 / 100000.0

RW Real

99

VEncdls FReg Ki
Encoderless Vector, Frequency Regulator Integral Gain
Determined during autotuning when P35 [Motor Ctrl Mode] is set to one of the FV
modes without speed feedback. Represents voltage compensation dependent on motor
cable and PWM Frequency.

Units:
Default:
Min/Max:

Hz/A
9080.0
0.0 / 100000.0

RW Real

100

Slip Reg Enable
Slip Regulator Enable
Enables or disables the slip frequency regulator. This selection is active only in motor
control mode flux vector induction (P35 [Motor Ctrl Mode] = 3 “Induction FV”) and
encoder feedback is used.

Default:
Options:

1 = “Enabled”
0 = “Disabled”
1 = “Enabled”

RW 32-bit

Integer

101

Slip Reg Ki
Slip Regulator Integral Gain
Integral gain for the slip frequency regulator.

Default:
Min/Max:

10.00
0.00 / 10000.00

RW Real

102

Slip Reg Kp
Slip Regulator Proportional Gain
Proportional gain for the slip frequency regulator.

Default:
Min/Max:

0.50
0.00 / 10000.00

RW Real

103

Flux Reg Enable
Flux Regulator Enable
Enables or disables the flux regulator. This selection is active only in motor control mode
flux vector induction (P35 [Motor Ctrl Mode] = 3 “Induction FV”).

Default:
Options:

1 – Enabled
0 – Disabled
1 – Enabled

RW 32-bit

Integer

104

Flux Reg Ki
Flux Regulator Integral Gain
Integral gain for the flux regulator.

Default:
Min/Max:

30.00
0.00 / 10000.00

RW Real

105

Flux Reg Kp
Flux Regulator Proportional Gain
Proportional gain for the flux regulator.

Default:
Min/Max:

1.00
0.00 / 10000.00

RW Real

753
755

753
755