Troubleshooting

4.

Energize the drive.

With the addition of a drive assembly, port verification errors indicate the
number of installed drive assemblies. For example, a frame 9 would
indicate “Two Inverters” and “Two Converters.”

5.

On the HIM press FIX to acknowledge the error then Enter to confirm.

An F361 “Rerate See Manual” fault is indicated.

6.

Verify the new rating shown in Port 10, P21 [Effctv I Rating].

Set Port 10, P20 [Recfg Acknowledg] to 1 “Acknowledge” to accept the
reconfiguration.

7.

Press the Stop key on the HIM to clear the fault.

P20 [Recfg Acknowledg] automatically returns to 0 “Ready.”

8.

Use the HIM download function, DriveExecutive download function, or
DriveExplorer download function to download the parameter settings
saved in Step1.

9.

Run the drive at the full rating and full power limits.

IMPORTANT

Drive parameters are set to factory defaults when reconfiguration is
acknowledged. If a condition exists that does not allow the drive
parameters to be set to factory defaults, setting P20 to 1
“Acknowledge” will not be accepted. Such conditions include the drive
is currently running, DeviceLogix is currently running, or the drive is
communicating with a PLC.

IMPORTANT

Do not use the Compare Screen Copy function in DriveExecutive or the
Error Check Download function in DriveExplorer to perform this step.