Rockwell Automation Publication 750-PM001J-EN-P - October 2014

185

Drive Port 0 Parameters

Chapter 3

APPLIC

AT

IO

NS

Pump O

ff

1196

Pump Off Speed
Pump Off Speed
Sets the percent drop in speed from the commanded speed during a pump off condition.

Units:
Default:
Min/Max:

%
20.00
0.00 / 100.00

RW Real

1197

Pump Off Time
Pump Off Time
Sets the time the drive will run at the reduced P1196 [Pump Off Speed] before returning
to the commanded speed and checking if the pump off condition still exists.

Units:
Default:
Min/Max:

Secs
600.00
120.00 / 60000.00

RW Real

1198

Pct Cycle Torque
Percent Cycle Torque
Displays the average torque for a full pump cycle.

Units:
Default:
Min/Max:

%
0.00
-100.00 / 200.00

RO

Real

1199

Pct Lift Torque
Percent Lift Torque
Displays the average rod lift torque.

Units:
Default:
Min/Max:

%
0.00
-100.00 / 200.00

RO

Real

1200

Pct Drop Torque
Percent Drop Torque
Displays the average rod dropping torque.

Units:
Default:
Min/Max:

%
0.00
-100.00 / 200.00

RO

Real

1201

Stroke Pos Count
Stroke Position Count
Displays the pump cycle position. The top of stroke should be 0 and rolls over at 10,000.

Default:
Min/Max:

0
0 / 15000

RO

32-bit
Integer

1202

Stroke Per Min
Stroke Per Minute
Displays the strokes per minute.

Default:
Min/Max:

0.00
0.00 / 50.00

RO

Real

1203

Pump Off Count
Pump Off Count
Displays the number of times a pump off condition has occurred since this parameter
was reset.

Default:
Min/Max:

0.00
0.00 / 60000.00

RW Real

1204

PumpOff SleepCnt
Pump Off Sleep Count
Displays the number of times a sleep condition has occurred since this parameter was
reset.

Default:
Min/Max:

0.00
0.00 / 60000.00

RW Real

1205

Day Stroke Count
Day Stroke Count
Displays the number of strokes for the past 24 hours. This is a rolling counter updated
every hour.

Default:
Min/Max:

0.00
0.00 / 65535.00

RO

Real

1206

DI PumpOff Disbl
Digital Input Pump Off Disable
Selects the digital input source for the Pump Off Disable function.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

1207

Pump OffSleepLvl
Pump Off Sleep Level
Provides a source for P351 [SleepWake RefSel]. This provides the start/stop control of
the drive by the pump off function.

Units:
Default:
Min/Max:

Volt
0.00
0.00 / 10.00

RO

Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T