Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 222

Advertising
background image

222

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 4

Port 10 and Port 11 Parameters

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

CO

N

V

ER

TE

R

CO

M

M

O

N

Co

n

fi

gur

at

io

n

16

Gnd Cur Flt Lvl

Ground Current Fault Level
The converter system peak ground current fault threshold. The converter will fault if the
peak input ground current exceeds this threshold for five line cycles on any converter.

Units:
Default:
Min/Max:

Amps
600.0
0.0 / 3000.0

RW Real

755 (8+)

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

CO

N

V

ER

TE

R C

O

M

M

O

N

Meterin

g

20

L1 Phase Curr

Line 1 Phase Current
The converter system AC line 1 (R) RMS input current. This is the sum of all line 1 (R)
phase currents from all online converters.

Units:
Default:
Min/Max:

Amps
0.0
0.0 / 15000.0

RO

Real

21

L2 Phase Curr

Line 2 Phase Current
The converter system AC line 2 (S) RMS input current. This is the sum of all line 2 (S)
phase currents from all online converters.

Units:
Default:
Min/Max:

Amps
0.0
0.0 / 15000.0

RO

Real

22

L3 Phase Curr

Line 3 Phase Current
The converter system AC line 3 (T) RMS input current. This is the sum of all line 3 (T)
phase currents from all online converters.

Units:
Default:
Min/Max:

Amps
0.0
0.0 / 15000.0

RO

Real

23

Heatsink Temp

Heatsink Temperature
The converter system heatsink temperature. This is the maximum heatsink temperature
from all online converters.

Units:
Default:
Min/Max:

DegC
0.0
–/+200.0

RO

Real

24

SCR Temp

SCR Temperature
The converter system SCR temperature. This is the maximum SCR temperature from all
online converters.

Units:
Default:
Min/Max:

DegC
0.0
–/+200.0

RO

Real

25

Gate Board Temp

Gate Board Temperature
The converter system gate board temperature. This is the maximum gate board
temperature from all online converters

Units:
Default:
Min/Max:

DegC
0.0
–/+200.0

RO

Real

755 (8+)

755 (8+)

755 (8+)

755 (8+)

755 (8+)

755 (8+)

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

CO

N

V

ER

TE

R

C

O

M

M

O

N

Te

st

po

in

ts

30
32

Testpoint Sel 1
Testpoint Sel 2

Testpoint Selection 1, 2
Selects a source for [Testpoint Val n]. Used by the factory, typically for diagnostic
purposes.

Default:
Min/Max:

0
0 / 65535

RW 32-bit

Integer

31
33

Testpoint Val 1
Testpoint Val 2

Testpoint Value 1, 2
Displays data selected by [Testpoint Sel n].

Default:
Min/Max:

0.000000
–/+220000000.000000

RO

Real

755 (8+)
755 (8+)

755 (8+)
755 (8+)

Advertising