Chapter 6

Troubleshooting

244
245
246
247
248
249
250
251
252
253
254

Port 4 Cfg
Port 5 Cfg
Port 6 Cfg
Port 7 Cfg
Port 8 Cfg
Port 9 Cfg
Port 10 Cfg
Port 11 Cfg
Port 12 Cfg
Port 13 Cfg
Port 14 Cfg

Alarm 2

The main control board does not have the correct option in the port.
Option may not be compatible with product or MCB firmware needs to
be updated to support it. Option my have to be moved or removed,
accept option configuration change.

264
265
266
267
268
269
270
271
272
273
274

Port 4 Checksum
Port 5 Checksum
Port 6 Checksum
Port 7 Checksum
Port 8 Checksum
Port 9 Checksum
Port10 Checksum
Port11 Checksum
Port12 Checksum
Port13 Checksum
Port14 Checksum

Resettable
Fault

Coast

A option module storage checksum failed.
Option data has been set to default values.

281

Enet Checksum

Resettable
Fault

Coast

EtherNet/IP storage checksum failed. Data set to default values.

282

DLX Checksum

Resettable
Fault

Coast

DeviceLogix storage checksum failed. Data set to default values.

290

Prev Maint Reset

Alarm 1

Predictive maintenance function has reset an elapsed life parameter.

291

HSFan Life

Configurable

493

[HSFan EventActn]

Predictive maintenance function has reached the event level. Perform
maintenance.

292

InFan Life

Configurable

500

[InFan EventActn]

293

MtrBrng Life

Configurable

506

[MtrBrngEventActn]

294

MtrBrng Lube

Configurable

510

[MtrLubeEventActn]

295

MachBrng Life

Configurable

515

[MtrBrngEventActn]

296

MachBrng Lube

Configurable

519

[MchLubeEventActn]

307

Port7InvalidCard

Non-Reset
Fault

Coast

Option not valid in that port. Remove option module.

308

Port8InvalidCard

Non-Reset
Fault

Coast

315

Excess Psn Err

Configurable

Configured with Logix
controller.

The absolute maximum Position Error value has been exceeded.

318
319
320

OutCurShare PhU
OutCurShare PhV
OutCurShare PhW

Alarm 1

There is output current sharing imbalance between parallel inverters in
the phase indicated that is greater than 15% of the inverter rated
current.

322

N-1 Operation

Alarm 1

20

(Port 10)

[Recfg Acknowledg]

21

(Port 10)

[Effctv I Rating]

Drive is operating with fewer inverters than the original parallel
configuration.

324

DC Bus Mismatch

Non-Reset
Fault

Coast

There is a bus voltage imbalance between parallel inverters that is
greater than 50V DC.

327
328
329

HS Temp Imbal U
HS Temp Imbal V
HS Temp Imbal W

Alarm 1

There is a heatsink temperature imbalance between parallel inverters in
the phase indicated that is greater than 11.5 °C (52.7 °F).

Event
No.

Fault/Alarm Text

Type

Fault
Action

Configuration
Parameter

Auto
Reset

Description/Action(s)