Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 260

Advertising
background image

260

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 5

Embedded Feature and Option Module Parameters

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

22-S

eries I/O

Mo

to

r PT

C

40

PTC Cfg
Positive Temperature Coefficient Configuration
Sets the action that will be taken when the PTC is not Ok.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.

Default:
Options:

0 = “Ignore”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop”
5 = “Flt CL Stop”

RW 32-bit

Integer

41

PTC Sts
Positive Temperature Coefficient Status

RO

16-bit
Integer

Status of the PTC.

Bit 0 “PTC Ok” – PTC is OK
Bit 1 “PTC Short” – PTC is Shorted
Bit 2 “Over Temp” – PTC is indicating over temperature

42

PTC Raw Value
Positive Temperature Coefficient Raw Value
Displays the value of the PTC.

Units:
Default:
Min/Max:

Volt
0
0 / 10

RO

Real

Options

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Res

er

ved

Ov

er

T

em

p

PT

C Sh

or

t

PT

C O

k

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

22-S

eries I/O

An

al

og In

put

s

45

Anlg In Type
Analog Input Type

RO

16-bit
Integer

Status of the analog input mode set by the option jumpers.

46

Anlg In Sqrt
Analog Input Square Root

RW 16-bit

Integer

Enables/disables the square root function for each input.

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Analog 1

Analog 0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Voltage Mode
1 = Current Mode

Options

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Analog 1

Analog 0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Square Root Disabled
1 = Square Root Enabled

Advertising