Torque prove – Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 452

Advertising
background image

452

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Appendix B

Application Notes

Torque Prove

Carefully perform the following steps in the order presented.

1.

Enter Torque Prove parameter settings.

Once Torque Prove is activated, the drive is in alarm state.

2.

Select the source of position feedback.

3.

Set the time to decrease motor torque during Brake Slip test.

4.

Set speed deviation.

Increase this setting if the drive faults on F20 [TorqPrv Spd Band].

5.

Set speed deviation level.

Increase this setting if the drive faults on F20 [TorqPrv Spd Band].

6.

Set brake release time.

Increase or decrease this setting depending on the time that is required to
open the brake.

7.

Set brake set time.

Increase or decrease this setting depending on the time that is required to
close the brake.

8.

Set allowable brake slip.

Sets the number of motor revolutions the motor is allowed to lower the
load when a brake slip has been detected.

I/O Module Parameter (Port X)

Setting

P10 [RO0 Sel]

0.00 (Disabled)

P6 [Dig Out Invert]

Bit 0 “Relay Out 0” = 1 (Output Inverted)

P10 [RO0 Sel]

Port 0, P1103 [Trq Prove Status], Bit 4 “Brake Set” = 1

Drive Parameter

Setting

P1100 [Trq Prove Cfg]

Bit 0 “TP Enable” = 1

Drive Parameter

Setting

P135 [Psn Fdbk Sel]

Encoder Port Number, P4 [Enc 0 FB]

Drive Parameter

Setting

P1104 [Trq Lmt SlewRate]

10.000 Secs (Default)

Drive Parameter

Setting

P1105 [Speed Dev Band]

Start with default Hz or RPM.

Drive Parameter

Setting

P1106 [SpdBand Intgrtr]

0.060 Secs (Default)

Drive Parameter

Setting

P1107 [Brk Release Time]

0.100 Secs (Default)

Drive Parameter

Setting

P1108 [Brk Set Time]

0.100 Secs (Default)

Drive Parameter

Setting

P1109 [Brk Alarm Travel]

1.00 (Default)