Rockwell Automation Publication 750-PM001J-EN-P - October 2014

179

Drive Port 0 Parameters

Chapter 3

A

PPLI

CA

TION

S

Fi

be

rs

Fu

n

ct

io

n

1126

P Jump
Position Jump
Sets the amplitude of the square wave speed modulation for the Fiber Traverse function.
This speed is alternately added to and subtracted from the speed reference together
with the P1125 [Max Traverse] triangle speed modulation.

Units:

Default:
Min/Max:

Hz
RPM
0.00
0.00 / P520 [Max Fwd Speed]

RW Real

1129

DI Fiber SyncEna
Digital Input Fiber Synchronize Enable
Selects a digital input source for the Fiber Application Function's synchronous speed
change routine. Used in combination with the P1120 [Fiber Control] Sync Enable bit.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

1130

DI Fiber TravDis
Digital Input Fiber Traverse Disable
Selects a digital input source for the Fiber Application Traverse Routine. This is an
inverted input, so the Traverse Routine is disabled when the input is active (set). Used in
combination with P1120 [Fiber Control] Bit 1 “Traverse Ena.”

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Rea

d-W

ri

te

Da

ta T

ype

APPLIC

AT

IONS

Adju

st

abl

e Vl

tg

1131

Adj Vltg Config
Adjustable Voltage Configuration

RW 16-bit

Integer

Selects output voltage phase setting. Single-phase operation is intended for resistive loads such as heating coils.
Connect single-phase loads across the U/T1 and V/T2 output terminals.

1133

Adj Vltg Select
Adjustable Voltage Reference Select
Selects the source of the voltage reference to the drive.

Default:
Min/Max:

0
0 / 159999

RW 32-bit

Integer

1134

Adj Vltg Ref Hi
Adjustable Voltage Reference High
Scales the upper value of the P1133 [Adj Vltg Select] selection when the source is an
analog input.

Units:
Default:
Min/Max:

%
0.0
–/+100.0 of Drive Rated Volts

RW Real

1135

Adj Vltg Ref Lo
Adjustable Voltage Reference Low
Scales the lower value of the P1133 [Adj Vltg Select] selection when the source is an
analog input.

Units:
Default:
Min/Max:

%
0.0
–/+100.0 of Drive Rated Volts

RW Real

1136

Adj Vltg TrimSel
Adjustable Voltage Trim Select
Selects the source of the voltage trim that is added to or subtracted from the voltage
reference.

Default:
Min/Max:

0
0 / 159999

RW 32-bit

Integer

1137

Adj Vltg Trim Hi
Adjustable Voltage Trim High
Scales the upper value of the P1136 [Adj Vltg TrimSel] selection when the source is an
analog input.

Units:
Default:
Min/Max:

%
0.0
–/+100.0 of Drive Rated Volts

RW Real

1138

Adj Vltg Trim Lo
Adjustable Voltage Trim Low
Scales the lower value of the P1136 [Adj Vltg TrimSel] selection when the source is an
analog input.

Units:
Default:
Min/Max:

%
0.0
–/+100.0 of Drive Rated Volts

RW Real

Options

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Phase

Setting

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = 3-Phase Operation
1 = 1-Phase Operation

Advertising