Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 89

Advertising
background image

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

89

Drive Port 0 Parameters

Chapter 3

DR

IVE CFG

Au

to M

an

u

al Ct

rl

329

Alt Man Ref AnHi
Alternate Manual Reference Analog High
Hi scale for the alternate manual speed reference when P328 [Alt Man Ref Sel] is
connected to an Analog Input.

Units:

Default:
Min/Max:

Hz
RPM
P520
P521 / P520

RW Real

330

Alt Man Ref AnLo
Alternate Manual Reference Analog Low
Lo scale for the alternate manual speed reference when P328 [Alt Man Ref Sel] is
connected to an Analog Input.

Units:

Default:
Min/Max:

Hz
RPM
0
P521 / P520

RW Real

331

Manual Preload
Manual Preload

RW 16-bit

Integer

Enables/disables automatic preloading of the “Auto” speed reference into a HIM when the HIM has been granted Manual control while in Auto mode. See P935
[Drive Status 1] Bit 9 “Manual” to verify the operating condition of the drive. Important: Preload will only occur if the transfer from auto to manual is done while
the drive is running.

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Po

rt

3

Po

rt

2

Po

rt

1

Re

se

rv

ed

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

DR

IV

E C

FG

Driv

e Mem

or

y

336

Reset Meters
Reset Meters
Resets selected meters to zero. The value will automatically be returned to 0.
“MWH and kWh” (1) – Resets P13 [Elapsed MWH], P14 [Elapsed kWH], P16 [Elpsd Mtr
MWHrs], P17 [Elpsd Rgn MWHrs], P18 [Elpsd Mtr kWHrs], and P19 [Elpsd Rgn kWHrs].
“Elapsed Time” (2) – Resets P15 [Elapsed Run Time].

Default:
Options:

0 = “Ready”
0 = “Ready”
1 = “MWH and kWh”
2 = “Elapsed Time”

RW 32-bit

Integer

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Read-W

rite

Da

ta

T

yp

e

DR

IVE CFG

St

ar

t F

ea

tur

es

345

Start At PowerUp
Start At Power Up
Enables/disables a feature to issue a Run command and automatically resume running
at commanded speed after drive input power is restored. Requires a digital input, P163
[DI Run], P164 [DI Run Forward], or P165 [DI Run Reverse], is configured for Run and a
valid start contact.

Default:
Options:

0 = “Disabled”
0 = “Disabled”
1 = “Enabled”

RW 32-bit

Integer

346

PowerUp Delay
Power Up Delay
Defines the programmed delay time, in seconds, before a start command is accepted
after power up.

Units:
Default:
Min/Max:

Secs
0.00
0.00 / 10800.00

RW Real

ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate
application. Do not use this function without considering applicable local, national and international codes, standards,
regulations or industry guidelines.