Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 5

Embedded Feature and Option Module Parameters

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

Sa

fe

S

pee

d

Mo

ni

tor

Max Speed

61

Max Speed Enable
Maximum Speed Enable
Enable Safe Maximum Speed Monitoring.

Default:
Options:

0 = “Disable”
0 = “Disable”
1 = “Enable”

RW 8-bit

Integer

62

Safe Max Speed
Safe Maximum Speed
Defines the maximum speed limit that will be tolerated if Safe Maximum Speed
monitoring is enabled.

Units:

Default:
Min/Max:

RPM
mm/s
0
0 / 65535 RPM
0 / 65535 mm/s

RW 16-bit

Integer

63

Max Spd Stop Typ
Maximum Speed Stop Type
Defines the safe stop type that will be initiated in the event of a SMS Speed Fault.
“Torque Off” (0) – Safe Torque Off With Standstill Checking
“Safe Stp Typ” (1) – Safe Torque Off Without Standstill Checking

Default:
Options:

0 = “Torque Off”
0 = “Torque Off”
1 = “Safe Stp Typ”

RW 8-bit

Integer

64

Max Accel Enable
Maximum Acceleration Enable
Enable Safe Maximum Acceleration Monitoring.

Default:
Options:

0 = “Disable”
0 = “Disable”
1 = “Enable”

RW 8-bit

Integer

65

Safe Accel Limit
Safe Acceleration Limit
Defines the Safe Maximum Acceleration Limit, relative to encoder 1, for which the
system is being monitored.
Units are based on rotary or linear configuration defined by P29 [Fbk 1 Units].

Units:

Default:
Min/Max:

Rev/s

2

mm/s

2

0
0 / 65535 rev/s

2

0 / 65535 mm/s

2

RW 16-bit

Integer

66

Max Acc Stop Typ
Maximum Acceleration Stop Type
Defines the safe stop type that will be initiated in the event of an Acceleration Fault.
“Torque Off” (0) – Safe Torque Off With Standstill Checking
“Safe Stp Typ” (1) – Safe Torque Off Without Standstill Checking

Default:
Options:

0 = “Torque Off”
0 = “Torque Off”
1 = “Safe Stp Typ”

RW 8-bit

Integer