Drive Port 0 Parameters

Chapter 3

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

FEEDBA

CK & I/O

R0 P

redic

t Ma

in

285

RO PredMaint Sts

Relay Output Predictive Maintenance Status

RO

16-bit
Integer

Status of relay 0 predictive maintenance. When the condition of the bit = 1, the predicted relay life has elapsed.

286

RO0 Load Type

Relay Output 0 Load Type
Sets the type of load that will be applied to the relay. Must be properly set for the
Predictive Maintenance function to predict the relay life.

Default:
Options:

1 = “DC Inductive”
0 = “DC Resistive”
1 = “DC Inductive”
2 = “AC Resistive”
3 = “AC Inductive”

RW 32-bit

Integer

287

RO0 Load Amps

Relay Output 0 Load Amps
Load current that will be applied to the relay contacts. Must be properly set for the
Predictive Maintenance function to approximate the relay life.

Units:
Default:
Min/Max:

Amps
2.000
0.000 / 2.000

RW Real

288

RO0 TotalLife

Relay Output 0 Total Life
Total life cycles of the relay based on programmed load type and amps.

Units:
Default:
Min/Max:

Cycl
0
0 / 2147483647

RO

32-bit
Integer

289

RO0 ElapsedLife

Relay Output 0 Elapsed Life
Non-resettable, total accumulated cycles of the relay.

Units:
Default:
Min/Max:

Cycl
0
0 / 2147483647

RO

32-bit
Integer

290

RO0 RemainLife

Relay Output 0 Remaining Life
The difference between the Total Life and the Elapsed Life.

Units:
Default:
Min/Max:

Cycl
0
–/+2147483647

RO

32-bit
Integer

291

RO0 LifeEvntLvl

Relay Output 0 Life Event Level
Sets the percentage of relay life cycles before action is taken.

Units:
Default:
Min/Max:

%
80.000
0.000 / 100.000

RW Real

292

RO0 LifeEvntActn

Relay Output 0 Life Event Action
Sets the action that will be taken when the percentage of relay life cycles has been
reached.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.

Default:
Options:

1 = “Alarm”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop”
5 = “Flt CL Stop”

RW 32-bit

Integer

753

Options

Mast

er

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

la

y O

ut 0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True

753

753

753

753

753

753

753