Rockwell Automation Publication 750-PM001J-EN-P - October 2014

491

Using DeviceLogix

Appendix C

Figure 89 - Two Input Four Position Selector Switch Logic Map

Discrete Inputs in the Drive are used for Inputs 1 and Input 2. Output A, B, C,
and D are linked to DeviceLogix Scratchpad Registers. This allows further
flexibility to modify the values of these outputs.

The resulting output can be linked to a parameter and used in supporting drive
applications, such as configuring multiple preset speeds and point to point
positioning. In this example, it controls Preset Speed 1.

Parameter Configuration

The following parameters are configured for this example:

Port Parameter
No.

Parameter

Value

Description

14.1

DLX Out 01

Port 0:Preset Speed 1

14.33

DLX DIP 1

Port 4: Dig In Status.Input 1

Digital input 1 from Selector
Switch

14.34

DLX DIP 2

Port 4: Dig In Status.Input 2

Digital input 2 from Selector
Switch

14.17

DLX In 01

Port 14: DLX Real SP1

Output A

14.18

DLX In 02

Port 14: DLX Real SP2

Output B

14.19

DLX In 03

Port 14: DLX Real SP3

Output C

14.20

DLX In 04

Port 14: DLX Real SP4

Output D

14.54

DLX Real SP1

75.00

Output A Preset Speed

14.55

DLX Real SP2

85.00

Output B Preset Speed

14.56

DLX Real SP3

95.00

Output C Preset Speed

14.57

DLX Real SP4

105.00

Output D Preset Speed

0.571

Preset Speed 1

varies

Resulting output from Selector
Switch

Digital Input 1

DLX

DIP 1

Digital Input 2

DLX

DIP 2

DLX

Out 1

00

01

10

11

Output A

Output B

Output C

Output D