Rockwell Automation Publication 750-PM001J-EN-P - October 2014

71

Drive Port 0 Parameters

Chapter 3

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

FEEDBA

CK & I/O

Digi

n F

u

n

cti

ons

150

Digital In Cfg
Digital Input Configure
Defines operation for DI Run type parameters.
Run Edge (0) – Control function requires a rising edge (open to close transition) in order
for the drive to run.
Run Level (1) – Provides a run level input. Does not require a transition for enable or
fault, but a transition is required for a stop.
When set to 1 “Run Level” the absence of a run command is indicated as a stop asserted
and parameter 935 [Drive Status 1] Bit 0 will be low.

Default:
Options:

0 – Run Edge
0 – Run Edge
1 – Run Level

RW 32-bit

Integer

155

DI Enable
Digital Input Enable
Assigns a digital input used to enable the drive.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

156

DI Clear Fault
Digital Input Clear Fault
Assigns a digital input used to clear faults.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

157

DI Aux Fault
Digital Input Auxiliary Fault
Assigns a digital input used to force an external auxiliary fault.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

158

DI Stop
Digital Input Stop
Assigns a digital input used to issue a stop command.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

159

DI Cur Lmt Stop
Digital Input Current Limit Stop
Assigns a digital input used to perform a current limited stop.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

160

DI Coast Stop
Digital Input Coast Stop
Assigns a digital input used to perform a coast-to-stop.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

161

DI Start
Digital Input Start
Assigns a digital input used to start the drive (3-wire control).

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

162

DI Fwd Reverse
Digital Input Forward Reverse
Assigns a digital input used to command reverse direction.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

163

DI Run
Digital Input Run
Assigns a digital input used to run the drive (2-wire control).

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

164

DI Run Forward
Digital Input Run Forward
Assigns a digital input used to run the drive (2 wire control) and command forward
direction.

Default:
Min/Max:

0.00
0.00 / 159999.15

RW 32-bit

Integer

ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate
application. Do not use this function without considering applicable local, national and international codes, standards,
regulations, or industry guidelines.