Chapter 3

Drive Port 0 Parameters

APPLIC

AT

IONS

A

dju

st

abl

e Vl

tg

1139

Adj Vltg Command
Adjustable Voltage Command
Displays the voltage value of the reference specified in P1133 [Adj Vltg Select].

Units:
Default:
Min/Max:

V AC
0.00
0.00 / Drive Rated Volts

RO

Real

1140

Adj Vltg AccTime
Adjustable Voltage Acceleration Time
Sets the rate of voltage increase. The value will be the time it takes to ramp the voltage
from P1152 [Min Adj Voltage] to P36 [Maximum Voltage]. An “S” curve can be applied
to the ramp using P1150 [Adj Volt Scurve].

Units:
Default:
Min/Max:

Secs
0.0
0.0 / 3600.0

RW Real

1141

Adj Vltg DecTime
Adjustable Voltage Deceleration Time
Sets the rate of voltage decrease. The value will be the time it takes to ramp the voltage
from P36 [Maximum Voltage] to P1152 [Min Adj Voltage]. An “S” curve can be applied
to the ramp using P1150 [Adj Volt Scurve]. This is an independent voltage ramp
decoupled from the scalar frequency ramp P537/538 [Decel Time n] and controlled by
user selectable acceleration and deceleration ramp times.
Important: This ramp and P537/538 [Decel Time n] must ramp to zero for drive to Stop.

Units:
Default:
Min/Max:

Secs
0.0
0.0 / 3600.0

RW Real

1142
1143
1144
1145
1146
1147
1148

Adj Vltg Preset1
Adj Vltg Preset2
Adj Vltg Preset3
Adj Vltg Preset4
Adj Vltg Preset5
Adj Vltg Preset6
Adj Vltg Preset7
Adjustable Voltage Preset n
Provides an internal fixed voltage command value that is available as a selection for
P1133 [Adj Vltg Select].

Units:
Default:
Min/Max:

V AC
0.0
0.0 / Based on Drive Rating and Voltage
Class

RW Real

1149

Adj Vltg RefMult
Adjustable Voltage Reference Multiplier
Scales the selected reference voltage by a percentage where 100% equals the reference
command. If the reference command equals 100V and P1149 equals 100% then the
total output voltage equals 100V + 100V = 200V.

Units:
Default:
Min/Max:

%
0.0
–/+100.0 of Drive Rated Volts

RW Real

1150

Adj Vltg Scurve
Adjustable Voltage S Curve
Sets the percentage of acceleration time or deceleration time to be applied to the
voltage ramp as “S” curve. Time is added 1/2 at the beginning and 1/2 at the end. A
value of zero disables this feature.

Units:
Default:
Min/Max:

%
0.0
0.0 / 100.0

RW Real

1151

Adj Vltg TrimPct
Adjustable Voltage Trim Percentage
Scales the selected trim voltage by a percentage where 100% equals the trim voltage. If
the reference command equals 100V and P1151 equals 100% then the total output
voltage equals 100V + 100V = 200V.
Analog In 1 and 2 are scaled separately with P1137 [Adj Vltg Trim Hi] and P1138 [Adj
Vltg Trim Lo] then P1151 sets the trim value. The sign of this value will determine if trim
is added or subtracted from the reference.

Units:
Default:
Min/Max:

%
0.0
–/+100.0 of Drive Rated Volts

RW Real

1152

Min Adj Voltage
Minimum Adjustable Voltage
Sets the low limit for the voltage reference when P35 [Motor Ctrl Mode] is set to 9 “Adj
Voltage.”

Units:
Default:
Min/Max:

V AC
0.0
0.0 / Drive Rated Volts

RW Real

1153

Dead Time Comp
Dead Time Compensation
Sets the dead time compensation value to reduce DC offsets in the output voltage from
the PWM inverter for non-motor loads.

Units:
Default:
Min/Max:

%
100.00
0.00 / 100.00

RW Real

1154

DC Offset Ctrl
DC Offset Control
Used to further reduce DC offsets in the output voltage from the PWM inverter for non-
motor loads. When enabled, P1153 [Dead Time Comp] is disabled.

Default:
Options:

0 = “Disable”
0 = “Disable”
1 = “Enable”

RW 32-bit

Integer

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype