Troubleshooting

Chapter 6

Setting Factory Defaults

The PowerFlex 20-HIM-A6 / -C6S HIM User Manual, publication

20HIM-

UM001

, provides detailed instructions on using Human Interface Module

capabilities including setting PowerFlex 750-Series drive to factory settings.

The following parameters are not reset when Set Defaults “Most” is executed:
P300 [Speed Units], P301 [Access Level], P302 [Language], P305 [Voltage
Class], P306 [Duty Rating], P471 [PredMaint Rst En], and P472 [PredMaint
Reset].

System Resource Allocation

Each option installed in the drive requires a percentage of the available system
resources. Some options configurations may exceed the available resources of the
main control board’s processor. If 90% of the available system resources is
reached, an F19 Task Overrun alarm will result indicating that system resource
utilization is excessive.

Table 8 - System Resource Allocation - Drive Frames 1…7

Table 9 - System Resource Allocation - Drive Frames 8…10

Sys

tem

Re

so

ur

ce

U

sa

ge

100%

90%

80%

70%

60%

Feedback Option Module = 3%

DIO Option Module = 3%

DeviceLogix Program = 1%

50%

Internal EtherNet/IP = 4%

Communication Option Module = 7%

40%

Base System Requirement = 40%

30%

20%

10%

Configuration Option

Syste

m

Re

so

u

rc

e Usa

ge

100%

90%

Feedback Option Module = 5%

DIO Option Module = 5%

80%

DeviceLogix Program = 10%

70%

Internal EtherNet/IP = 10%

60%

Communication Option Module = 20%

50%

40%

Base System Requirement = 40%

30%

20%

10%

Configuration Option