Embedded Feature and Option Module Parameters

Chapter 5

Sa

fe

Speed Mon

it

or

Se

cu

ri

ty

70

Config Flt Code
Configuration Fault Code
0 = No Fault
1 = Password Required (Password Req)
2 = P21 [Safety Mode] value not legal based on P20 [Cascaded Config] value.
3 = P57 [Door Out Type] value not legal based on P20 [Cascaded Config] value.
4 = P46 [Stop Mon Delay] value not legal based on P45 [Safe Stop Type] value.
5 = P50 [Decel Ref Speed] value not legal based on P31 [Fbk 1 Resolution] value.
6 = P48 [Standstill Speed] value not legal based on P20 [Cascaded Config] value.
7 = P53 [LimSpd Mon Delay] value not legal based on P21 [Safety Mode] value.
8 = P55 [Safe Speed Limit] value not legal based on P21 [Safety Mode] and P31 [Fbk 1
Resolution] value.
9 = P56 [Speed Hysteresis] value not legal based on P21 [Safety Mode] value.
10 = P62 [Safe Max Speed] value not legal based on P31 [Fbk 1 Resolution] value.
11 = P42 [Direction Mon] value not legal based on P21 [Safety Mode] value.
12 = P59 [Lock Mon Enable] value not legal based on P21 [Safety Mode] value.
13 = P36 [Fbk 2 Resolution] value not legal based on P27 [Fbk Mode] value.
14 = P35 [Fbk 2 Polarity] value not legal based on P27 [Fbk Mode] value.
15 = P39 [Fbk Speed Ratio] value not legal based on P27 [Fbk Mode] value.
16 = P41 [Fbk Pos Tol] value not legal based on P27 [Fbk Mode] value.
17 = P40 [Fbk Speed Tol] value not legal based on P27 [Fbk Mode] value.
18 = P44 [Safe Stop In Typ] value not legal based on P21 [Safety Mode] value.
19 = P52 [Lim Spd In Typ] value not legal based on P21 [Safety Mode] value.
20 = P58 [DM Input Type] value not legal based on P20 [Cascaded Config] and P21
[Safety Mode] value.
21 = P54 [Enable SW In Typ] value not legal based on P21 [Safety Mode] value.
22 = P60 [Lock Mon In Type] value not legal based on P21 [Safety Mode] value and P59
[Lock Mon Enable] value.
23 = Illegal P20 [Cascaded Config] value.
24 = Illegal P22 [Reset Type] value.
25 = Reserved
26 = Illegal P45 [Safe Stop Type] value.
27 = Illegal P51 [Stop Decel Tol] value.
28 = Illegal P27 [Fbk Mode] value.
29 = Illegal P28 [Fbk 1 Type] value.
30 = Illegal P31 [Fbk 1 Resolution] value.
31 = Illegal P32 [Fbk1 Volt Mon] value.
32 = Illegal P37 [Fbk 2 Volt Mon] value.
33 = Illegal P24 [OverSpd Response] value.
34 = Reserved
36 = Unknown Error (Unknown Err).

Default:
Options:

NA
0…36

RO

8-bit
Integer

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype