Chapter 6

Troubleshooting

Drive does not Start from HIM.

Drive does not respond to changes in speed command.

Motor and/or drive will not accelerate to commanded speed.

Motor operation is unstable.

Cause(s)

Indication

Corrective Action

Drive is configured for 2 wire level
control.

None

Change P150 [Digital In Conf] to correct control
function.

Another device has Manual control.

None

Port does not have control.

None

Change P324 [Logic Mask] to enable correct port.

Cause(s)

Indication

Corrective Action

No value is coming from the source of
the command.

LCD HIM Status
Line indicates “At
Speed” and
output is 0 Hz.

1. If the source is an analog input, check wiring and

use a meter to check for presence of signal.

2. Check P2 [Commanded SpdRef] for correct source.

(See page 52)

Incorrect reference source has been
programmed.

None

3. Check P545 [Spd Ref A Sel] for the source of the

speed reference.

(See page 113)

4. Reprogram P545 [Spd Ref A Sel] for correct source.

(See page 113)

Incorrect Reference source is being
selected via remote device or digital
inputs.

None

5. Check P935 [Drive Status 1],

page 156

, bits 12 and

13 for unexpected source selections.

6. Check P220 [Digital In Sts],

page 76

to see if inputs

are selecting an alternate source.

7. Check configuration of P173…175 [DI Speed Sel

n] functions

Cause(s)

Indication

Corrective Action

Acceleration time is excessive.

None

Reprogram P535/536 [Accel Time X].

(See page 112)

Excess load or short acceleration times
force the drive into current limit,
slowing or stopping acceleration.

None

Check P935 [Drive Status 1], bit 27 to see if the drive is
in Current Limit.

(See page 156)

Remove excess load or reprogram P535/536 [Accel
Time n].

(See page 112)

Speed command source or value is not
as expected.

None

Check for the proper Speed Command using Steps 1
through 7 above.

Programming is preventing the drive
output from exceeding limiting values.

None

Check P520 [Max Fwd Speed], P521 [Max Rev Speed]

(See page 111)

and P37 [Maximum Freq]

(See

page 55)

to assure that speed is not limited by

programming.

Cause(s)

Indication

Corrective Action

Motor data was incorrectly entered or
Autotune was not performed.

None

1. Correctly enter motor nameplate data.
2. Perform “Static Tune” or “Rotate Tune” Autotune

procedure. See P70 [Autotune] on

page 61