Chapter 6

Troubleshooting

11158
11258
11358

P1 BFuse Pos
P2 BFuse Pos
P3 BFuse Pos

Non-Reset
Fault

Coast

The DC+ bus fuse is blown.

Check the DC+ bus fuse and wiring harness and replace if necessary.
If this problem persists, replace the converter gate firing board.

11159
11259
11359

P1 BFuse Neg
P2 BFuse Neg
P3 BFuse Neg

Non-Reset
Fault

Coast

The DC- bus fuse is blown.

Check the DC- bus fuse and wiring harness and replace if necessary.
If this problem persists, replace the converter gate firing board.

11160
11260
11360

P1 Command Stop
P2 Command Stop
P3 Command Stop

Resettable
Fault

Coast

Y

The main control board has commanded the converter gate firing board
to stop due to an asymmetrical bus condition.

Check the DC bus connections and wiring.

11163
11263
11363

P1 Fault Q Full
P2 Fault Q Full
P3 Fault Q Full

Resettable
Fault

Coast

The fault queue is full. There are at least three other faults in the queue.

Troubleshooting and clearing the existing faults will make room for

additional faults in the queue (if any).

Event
No.

Fault/Alarm Text

Type

Fault
Action

Configuration
Parameter

Auto
Reset

Description/Action(s)