Rockwell Automation Publication 750-PM001J-EN-P - October 2014

135

Drive Port 0 Parameters

Chapter 3

POSITION

C

O

N

TR

O

L

Po

si

ti

on

Cf

g/S

ts

727

In Pos Psn Dwell
In Positive Position Dwell
Sets dwell time for the in position detector. Position error must be within the value
specified by the in-position band P726 [In Pos Psn Band] for this amount of time before
the in-position detector sets the in-position detect bit P724 [Psn Reg Status] Bit 11
“InPsn Detect.” A momentary out-of-position indication will reset the internal timer and
clear the in-position detect bit P724 [Psn Reg Status] Bit 11 “InPsn Detect.”

Default:
Min/Max:

0.0040
0.0001 / 10.0000

RW Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype