Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Appendix B

Application Notes

3.

Configure the message instructions.
a. Click the Configuration tab. See

Figure 81

.

Figure 81 - Message Configuration Screen - Configuration Tab

b. In the Message Type field, click the down arrow to select CIP Generic.
c. In the Service Type field, click the down arrow to select Get Attribute

Single.

d. In the Class field, enter 93 (hex); use the EtherNet/IP DPI Parameter

Object.

e. Set the Instance to 482. This field defines the parameter that you want

to obtain.

f. Set the Attribute to 9. This field defines that you want to retrieve the

parameter value.

g. Click the Communication tab. See

Figure 82

.

Figure 82 - Message Configuration Screen - Communications Tab