25

Motor NP Volts
Motor Nameplate Volts
Rated volts shown on the motor nameplate.

Units:
Default:
Min/Max:

V AC
Based on Drive Rating and Voltage Class
0.10 / Based on Drive Rating and Voltage Class

RW Real

26

Motor NP Amps
Motor Nameplate Amps
Rated full load amps shown on the motor nameplate.

Units:
Default:
Min/Max:

Amps
Based on Drive Rating
0.01 / 14200.00

RW Real

27

Motor NP Hertz
Motor Nameplate Hertz
Rated frequency shown on the motor nameplate.

Units:
Default:
Min/Max:

Hz
Based on Drive Rating
2.00 / 650.00

RW Real

28

Motor NP RPM
Motor Nameplate Revolutions Per Minute
Rated RPM shown on the motor nameplate.

Units:
Default:
Min/Max:

RPM
Based on Drive Rating
1.0 / 40000.0

RW Real

29

Mtr NP Pwr Units
Motor Nameplate Power Units
Power units shown on the motor nameplate.

Default:
Options:

Based on Drive Rating
0 – HP
1 – kW

RW 32-bit

Integer

30

Motor NP Power
Motor Nameplate Power
Rated power shown on the motor nameplate.

Units:

Default:
Min/Max:

HP (P29 = 0)
kW (P29 = 1)
Based on Drive Rating
0.00 / 2000.00

RW Real

31

Motor Poles
Motor Poles
Number of poles in the motor.

Units:
Default:
Min/Max:

Pole
4
2 / 200

RW 32-bit

Integer

120 x [Motor NP Hertz]

[Motor NP RPM]

Poles =