Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 219

Advertising
background image

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

219

Port 10 and Port 11 Parameters

Chapter 4

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

IN

VERTER N

Meteri

ng

115
215
315

I1 U Phase Curr
I2 U Phase Curr
I3 U Phase Curr

Inverter n U Phase Current
Output current present through terminal T1 (U phase) of inverter n.

Units:
Default:
Min/Max:

Amps
0.0
–/+3000.0

RO

Real

116
216
316

I1 V Phase Curr
I2 V Phase Curr
I3 V Phase Curr

Inverter n V Phase Current
Output current present through terminal T2 (V phase) of inverter n.

Units:
Default:
Min/Max:

Amps
0.0
–/+3000.0

RO

Real

117
217
317

I1 W Phase Curr
I2 W Phase Curr
I3 W Phase Curr

Inverter n W Phase Current
Output current present through terminal T3 (W phase) of inverter n.

Units:
Default:
Min/Max:

Amps
0.0
–/+3000.0

RO

Real

118
218
318

I1 Gnd Current
I2 Gnd Current
I3 Gnd Current

Inverter n Ground Current
Ground current of the AC output to a motor. The value is calculated based on the output
currents (U, V, and W phases) for inverter n. When the three phases are balanced, the
ground current is ideally close to zero.

Units:
Default:
Min/Max:

Amps
0.0
–/+3000.0

RO

Real

119
219
319

I1 DC Bus Volt
I2 DC Bus Volt
I3 DC Bus Volt

Inverter n DC Bus Voltage
DC bus voltage measured by inverter n.

Units:
Default:
Min/Max:

V DC
0.00
0.00 / 1200.00

RO

Real

120
220
320

I1 Heatsink Temp
I2 Heatsink Temp
I3 Heatsink Temp

Inverter n Heatsink Temperature
Temperature of the heatsink for inverter n.

Units:
Default:
Min/Max:

DegC
0.0
–/+200.0

RO

Real

121
221
321

I1 IGBT Temp
I2 IGBT Temp
I3 IGBT Temp

Inverter n IGBT Temperature
IGBT junction temperature of inverter n.

Units:
Default:
Min/Max:

DegC
0.0
–/+200.0

RO

Real

124
224
324

I1 HSFan Speed
I2 HSFan Speed
I3 HSFan Speed

Inverter n Heatsink Fan Speed
The measured speed of the heatsink fan for inverter n.

Units:
Default:
Min/Max:

RPM
0.0
0.0 / 7200.0

RO

Real

125
225
325

I1 InFan 1 Speed
I2 InFan 1 Speed
I3 InFan 1 Speed

Inverter n Internal Fan 1 Speed
The measured speed of internal stirring fan 1 for inverter n.

Units:
Default:
Min/Max:

RPM
0.0
0.0 / 7200.0

RO

Real

126
226
326

I1 InFan 2 Speed
I2 InFan 2 Speed
I3 InFan 2 Speed

Inverter n Internal Fan 2 Speed
The measured speed of internal stirring fan 2 for inverter n.

Units:
Default:
Min/Max:

RPM
0.0
0.0 / 7200.0

RO

Real

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

755 (8+)
755 (8+)
755 (8+)

Advertising