Rockwell Automation Publication 750-PM001J-EN-P - October 2014

497

Using DeviceLogix

Appendix C

Example logic requirements:

If Critical High Level or High Level sensor is ON, then start the drive.

If Critical High Level sensor is ON, then switch to higher rate (90Hz)
for the rest of the pumping cycle. Else run at the normal rate (60Hz)

Run until all three level sensors are OFF

Pump should run at least ‘x’ minutes at a minimum. If the Low Level
sensor fails, this prevents the High Level sensor from cycling the pump
On/Off too quickly.

Annunciate a Sensor Fault condition

The Low Level sensor should never be OFF when either the High Level
or Critical High Level sensors are ON

The High Level sensor should never be OFF when the Critical High
Level sensor is ON

The Critical High Level sensor should never be ON when either the
High Level or Low Level sensors are OFF

Annunciate a Critical High Level condition

The Critical High Level output should never be ON

Annunciate if pumping cycle time is longer than normal (‘y’ minutes)

Monitor the amount of time a pump cycle takes by timing how long the
drive is operating.

If greater than ‘y’ minutes, energize the Too Much Time Alarm output

Reset alarms / faults with a Reset pushbutton input

Parameter Configuration

The following parameters are configured for this example.

The following DeviceLogix parameters are configured for this example:

Port Parameter
No.

Parameter

Value

Description

0.520

Max Fwd Speed

90.00

0.545

Speed Ref A Sel

Port 0: Preset Speed 1

0.571

Preset Speed 1

60.00

Normal pumping rate (60Hz)

0.573

Preset Speed 3

90.00

High speed pumping rate (90Hz)

4.10

RO0 Select

Port 14: DLX DigOut Sts2.DLX
DOPSts0

Sensor Fault output

4.20

TO0 Select

Port 14: DLX DigOut Sts2.DLX
DOPSts1

Critical High Level Fault output

4.30

TO1 Select

Port 14: DLX DigOut Sts2.DLX
DOPSts2

Too Much Time Alarm output

14.33

DLX DIP 1

Port 4: Dig In Status.Input 1

Critical High Level Sensor input

14.34

DLX DIP 2

Port 4: Dig In Status.Input 2

High Level Sensor input

14.35

DLX DIP 3

Port 4: Dig In Status.Input 3

Low Level Sensor input

14.36

DLX DIP 4

Port 4: Dig In Status.Input 4

Alarm / Fault Reset pushbutton
input