Drive Port 0 Parameters

PROTEC

TION

Predic

ti

ve

M

aintenance

511

MchBrngTotalLife
Machine Bearing Total Life
Total number of hours expected over the life of the machine bearings.

Units:
Default:
Min/Max:

Hrs
Current Value
0.00 / 21474836.47

RW 32-bit

Integer

512

MchBrngElpsdLife
Machine Bearing Elapsed Life
Accumulated hours of machine bearing run time.
Use P472 [PredMaint Reset] to reset this parameter.

Units:
Default:
Min/Max:

Hrs
0.00
0.00 / 21474836.47

RO

32-bit
Integer

513

MchBrngRemainLif
Machine Bearing Remaining Life
Remaining number of hours until estimated end of life for machine bearings, and is the
difference between Machine Bearing Total Life and Machine Bearing Elapsed Life.
Use P472 [PredMaint Reset] to reset this parameter.

Units:
Default:
Min/Max:

Hrs
0.00
–21474836.48 / 21474836.47

RO

32-bit
Integer

514

MchBrngEventLvl
Machine Bearing Event Level
Percent of total expected machine bearing life for which an early warning alarm or fault
can be programmed.

Units:
Default:
Min/Max:

%
80.000
0.000 / 100.000

RW Real

515

MchBrngEventActn
Machine Bearing Event Action
Configures the response to a machine bearing event, which occurs when P514
[MchBrngEventLvl] is met or exceeded.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.

Default:
Options:

0 = “Ignore”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop”
5 = “Flt CL Stop”

RW 32-bit

Integer

516

MchBrngResetLog
Machine Bearing Reset Log
Total number of resets performed on the P512 [MchBrngElpsdLife] parameter.

Default:
Min/Max:

0
0 / 255

RO

32-bit
Integer

517

MchLubeElpsdHrs
Machine Lubricant Elapsed Hours
Accumulated machine hours since the most recent lubrication of the machine bearings.
Can be reset without restriction.
Use P472 [PredMaint Reset] to reset this parameter.

Units:
Default:
Min/Max:

Hrs
0.00
0.00 / 21474836.47

RO

32-bit
Integer

518

MchLube EventLvl
Machine Lubricant Event Level
Number of hours between scheduled lubrications of the machine bearings. Used for an
early warning alarm or fault according to P519 [MchLubeEventActn]. Event is disabled
when set to 0.

Units:
Default:
Min/Max:

Hrs
0.000
0.000 / 2147483648.000

RW Real

519

MchLubeEventActn
Machine Lubricant Event Action
Configures the response to a machine bearing lubrication event, which occurs when
P518 [MchLube EventLvl] is met or exceeded.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.

Default:
Options:

0 = “Ignore”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop”
5 = “Flt CL Stop”

RW 32-bit

Integer

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype