Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 3

Drive Port 0 Parameters

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta T

ype

M

O

TO

R C

O

N

TROL

Vo

lt

s p

er

H

er

tz

60

Start Acc Boost
Start/Acceleration Boost
The voltage boost level for starting and acceleration when a “VHz” mode is selected,
according to P35 [Motor Ctrl Mode]. Refer to diagram for P524 [Overspeed Limit].

Units:
Default:
Min/Max:

V AC
Based on Drive Rating
0.00 / Based on Drive Rating and Voltage
Class

RW Real

61

Run Boost
Run Boost
The boost level for steady state and deceleration when a “VHz” mode is selected,
according to P35 [Motor Ctrl Mode]. Refer to diagram for P524 [Overspeed Limit].

Units:
Default:
Min/Max:

V AC
Based on Drive Rating
0.00 / Based on Drive Rating and Voltage
Class

RW Real

62

Break Voltage
Break Voltage
The voltage the drive will output at P63 [Break Frequency] when a “VHz” mode is
selected, according to P35 [Motor Ctrl Mode]. Refer to diagram for P524 [Overspeed
Limit].

Units:
Default:
Min/Max:

V AC
Based on Drive Rating and Voltage Class
0.00 / P25 [Motor NP Volts] x 1.5

RW Real

63

Break Frequency
Break Frequency
The frequency the drive will output at P62 [Break Voltage] when a “VHz” mode is
selected, according to P35 [Motor Ctrl Mode]. Refer to diagram for P524 [Overspeed
Limit].

Units:
Default:
Min/Max:

Hz
P27 [Motor NP Hertz] x 0.25
0.00 / P27 [Motor NP Hertz]

RW Real

This diagram (with P65 set to Custom V/Hz) depicts the Voltage to Frequency ratio when using the Induction VHz (0) motor control mode.

64

SVC Boost Filter
SVC Boost Filter
The voltage boost filter time constant when a “SVC” mode is selected, according to P35
[Motor Ctrl Mode].

Units:
Default:
Min/Max:

Secs
0.1000
0.0001 / 1000.0000

RW Real

65

VHz Curve
VHz Curve
Selects either a predefined curve (for example Fan/Pump), or a custom curve when a
“VHz” mode is selected, according to P35 [Motor Ctrl Mode]. Refer to diagram for P524
[Overspeed Limit].

Default:
Options:

0 – Custom V/Hz
0 – Custom V/Hz
1 – Fan/Pump

RW 32-bit

Integer

Frequency

Vo

ltage

P524

[Overspeed

Limit]

Frequency Trim due to
Speed Control Mode

P36 [Max Volts]

P25 [Motor Volts]

P61 [Run]

P62 [Break Volts]

P60 [Start Boost]

Allowable Output Frequency Range -

Normal Operation

Allowable Speed Reference Range

Allowable Output Frequency Range -

Bus Regulation or Current Limit

P37

[Max
Freq]

P27

[Motor Hz]

0

P63

[Break

Frequency]

Max

Speed

P520/P521
[FWD/REV]

Min

Speed

P522/P523
[FWD/REV]

Output

Freq Limit