16

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 1

Start Up

5.

The remainder of this procedure requires that a Human Interface Module
(HIM) is connected to DPI Port 1 or 2.

Figure 1 - DPI Ports and

6.

Apply AC power and control voltages to the drive.

If any digital inputs are configured to Stop – CF, Run, or Enable, verify
that signals are present or the drive will not start.

Refer to

Chapter 6

for

a list of potential digital input conflicts.

If the STS LED is not flashing green at this point, refer to

Drive Status

Indicators on page 18

.

7.

When prompted, select a display language. The Start-Up Screen will
automatically display for drives that have not been previously configured.

If the Start-Up screen is not displayed press the Enter key.

8.

Press the Enter key to display the Start-Up Menu.

9.

Use the Up/Down Arrow keys to highlight “2. Basic.”

10.

Press the Enter key. Follow the menu using the Enter key which will step
you through the Start-Up routine.

The Start-Up routine asks simple questions and prompts you to input
required information.