Chapter 3

Drive Port 0 Parameters

SPEED C

O

NTRO

L

Speed Re

gula

to

r

654

Spd Reg Int Out
Speed Regulator Integrator Output
Displays the current value of the vector speed regulator’s integral channel.
A value of 100% represents rated motor torque.

Units:
Default:
Min/Max:

%
0.00
–/+800.00

RO

Real

655

Spd Reg Pos Lmt
Speed Regulator Positive Limit
Adjusts the upper limit of the vector speed regulator’s output.
A value of 100% represents rated motor torque.

Units:
Default:
Min/Max:

%
300.00
0.00 / 600.00

RW Real

656

Spd Reg Neg Lmt
Speed Regulator Negative Limit
Adjusts the lower limit of the vector speed regulator’s output.
A value of 100% represents rated motor torque.

Units:
Default:
Min/Max:

%
–300.00
–600.00 / 0.00

RW Real

657

SReg OutFltr Sel
Speed Regulator Output Filter Select
Selects the amount of filtering applied to the vector speed regulator’s output. When set
to any of the custom settings (3, 4, or 5) the filter is configured using the values set in
P658 [SReg OutFltrGain] and P659 [SReg OutFltr BW]. Settings 4 and 5 initialize the
values for light and heavy respectively.

Default:
Options:

0 = “Off”
0 = “Off”
1 = “Light”
2 = “Heavy”
3 = “Custom”
4 = “SetCustLight”
5 = “SetCustHeavy”

RW 32-bit

Integer

658

SReg OutFltrGain
Speed Regulator Output Filter Gain
Sets the gain of the vector speed regulator’s output filter when P657 [SReg OutFltr Sel] is
set to one of the “Custom” settings (3, 4, or 5).
A gain value of zero results in a filter characteristic that behaves as a first order low pass.
A gain value ranging between zero and one results in a lag type filter. A gain value
greater than one results in a lead type filter. A gain value of one will disable (bypass) the
filter.

Default:
Min/Max:

1.000
–/+5.000

RW Real

659

SReg OutFltr BW
Speed Regulator Output Filter Bandwidth
Sets the bandwidth of the speed regulator’s output filter when P657 [SReg OutFltr Sel] is
set to one of the “Custom” settings (3, 4, or 5).
A value of zero will disable (bypass) the filter.

Units:
Default:
Min/Max:

R/S
35.00
0.00 / 3760.00

RW Real

660

SReg Output
Speed Regulator Output
Displays the output of the vector speed regulator. This signal will be routed to the P685
[Selected Trq Ref] when P313 [Actv SpTqPs Mode] has selected the output of the speed
regulator.
A value of 100% represents rated motor torque.

Units:
Default:
Min/Max:

%
0.00
–/+ 800.00

RO

Real

663

VHzSV Spd Reg Kp
Volts per Hertz Sensorless Vector Speed Regulator Proportional Gain
Adjusts the proportional gain of the Speed Regulator used in non-vector modes
according to P35 [Motor Ctrl Mode]. The output of this regulator will adjust P623 [VHzSV
SpdTrimReg] when P131 [Active Vel Fdbk] originates from a feedback device.

Default:
Min/Max:

20.00
0.00 / 3000.00

RW Real

664

VHzSV Spd Reg Ki
Volts per Hertz Sensorless Vector Speed Regulator Integral Gain
Adjusts the integral gain of the Speed Regulator used in non-vector modes according to
P35 [Motor Ctrl Mode]. The output of this regulator will adjust P623 [VHzSV
SpdTrimReg] when P131 [Active Vel Fdbk] originates from a feedback device.

Units:
Default:
Min/Max:

/Sec
50.00
0.00 / 100000.00

RW Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype