Cip motion error – Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 324

Advertising
background image

324

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 6

Troubleshooting

916

FPGA Failed to Load

Resettable
Fault

Coast

MCB failed to load on powerup.
Replace the main control board.

917

FPGA CRC Failure

Resettable
Fault

Coast

964

[CRC Flt Cfg]

only

Cycle power to clear this fault.
If fault does not clear, replace the main control board.

918

Control Task Overrun

Resettable
Fault

Coast

Carrier frequency changes when passing through 7 Hz.
In P40 [Mtr Option Cfg], set the PWM to 2 kHz or turn on the “PWM
FreqLock” Bit 9. Or flash the drive to 8.001.

919

System Task Overrun

Resettable
Fault

Coast

Control task not finished and being told to run again.
Cycle power to clear this fault. If fault does not clear, replace the main
control board.

920

5 mSec Task Overrun

Resettable
Fault

Coast

Control task not finished and being told to run again.
Cycle power to clear this fault. If fault does not clear, replace the main
control board.

921

Control Task Stall

Resettable
Fault

Coast

Control task stalled.
Check grounding or replace the main control board.

922

System Task Stall

Resettable
Fault

Coast

System task stalled.
Check grounding or replace the main control board.

923

5 mSec Task Stall

Resettable
Fault

Coast

5 msec task stalled.
Check grounding or replace the main control board.

924

Background Task Stall

Resettable
Fault

Coast

Background task stalled.
Check grounding or replace the main control board.

925

Stack Overflow

Resettable
Fault

Coast

Firmware overflow.
Obtain test points.

926

Ethernet Error

Resettable
Fault

Coast

Ethernet error.
Cycle power to clear this fault. Contact technical support.

927

CIP Motion Error

Resettable
Fault

Coast

Integrated motion error.
Cycle power to clear this fault. Contact technical support.

14037

Net IO Timeout

Configurable

52

[DLX Prog Cond]

DeviceLogix has been disabled.

Event
No.

Fault/Alarm Text

Type

Fault
Action

Configuration
Parameter

Auto
Reset

Description/Action(s)

753

IMPORTANT

Fault and Alarm event numbers between 3000 and 13999 are generated by a module installed in a port. Refer to

Fault and Alarm

Display Codes on page 312

for an explanation. For event numbers that fall between 13000 and 13999, refer to the PowerFlex 755

Drive Embedded EtherNet/IP Adapter User Manual, publication

750COM-UM001

for descriptions.