Chapter 5

Embedded Feature and Option Module Parameters

Safe Speed Monitor Module
Parameters

For detailed information on the Safe Speed Monitor option, refer to the Safe
Speed Monitor Option Module for PowerFlex 750-Series AC Drives Safety
Reference Manual, publication

750-RM001

.

Fi

le

Gro

u

p

No.

Display Name
Full Name
Description

Values

Read-W

ri

te

Da

ta

T

yp

e

Sa

fe

Spee

d Mo

nit

or

Secur

ity

1

Password
Password
Password for Lock and Unlock function.

Default:
Min/Max:

N/A
0 / 4294967295

RW 32-bit

Integer

5

Lock State
Lock State
Command to lock or unlock the safety option configuration.

Default:
Options:

0 = “Unlock”
0 = “Unlock”
1 = “Lock”

RW 8-bit

Integer

6

Operating Mode
Operating Mode
Command to place the system in Program or Run mode.

Default:
Options:

0 = “Program”
0 = “Program”
1 = “Run”
2 = “Config Fault”

RW 8-bit

Integer

7

Reset Defaults
Reset Defaults
Resets safety option to factory defaults.

Default:
Options:

0 = “No Action”
0 = “No Action”
1 = “Reset Fac” (Reset to factory defaults)

RW 8-bit

Integer

10

Signature ID
Signature Identifier
Safety configuration identifier.

Default:
Min/Max:

N/A
0 / 4294967295

RO

32-bit
Integer

13

New Password
New Password
32-Bit configuration password.

Default:
Min/Max:

N/A
0 / 4294967295

RW 32-bit

Integer

17

Password Command
Password Command
Save new password command.

Default:
Options:

0 = “No Action”
0 = “No Action”
1 = “Change PW” (Change Password)
2 = “Reset PW” (Reset Password)

RW 8-bit

Integer

18

Security Code
Security Code
Used for Reset Password command.

Default:
Min/Max:

N/A
0 / 65535

RO

32-bit
Integer

19

Vendor Password
Vendor Password
Vendor password for Reset Password command.

Default:
Min/Max:

N/A
0 / 65535

RW 16-bit

Integer