Troubleshooting

Chapter 6

Embedded EtherNet/IP (Port
13) Events

The adapter has an event queue to record significant events that occur in the
operation of the adapter. When such an event occurs, an entry consisting of the
event’s numeric code and a timestamp is put into the event queue. You can view
the event queue using the PowerFlex 20-HIM-A6/-C6S HIM, DriveExplorer
software (version 6.01 or later), DriveExecutive software (version 5.01 or later) or
other clients using the DPI Fault object. For details on viewing and clearing
events using the HIM, see the PowerFlex 20-HIM-A6/-C6S HIM (Human
Interface Module) User Manual, publication

20HIM-UM001

.

Many events in the event queue occur under normal operation. If you encounter
unexpected communications problems, the events may help you or Rockwell
Automation personnel troubleshoot the problem. The following events may
appear in the event queue.

Table 15 - Adapter Events

Table 16 - DPI Events

Table 17 - Network Events

Code

Event

Description

13001

No Event

Text displayed in an empty event queue entry.

13002

Device Power Up

Power was applied to the adapter.

13003

Device Reset

The adapter was reset.

13004

EEPROM CRC Error

The EEPROM checksum/CRC is incorrect, which limits adapter functionality.
Default parameter values must be loaded to clear this condition.

13005

App Updated

The adapter application firmware was flash updated.

13006

Boot Updated

The adapter boot firmware was flash updated.

13007…
13024

Reserved

Code

Event

Description

13025

DPI Manual Reset

The adapter was reset.

13026…
13028

Reserved

Code

Event

Description

13029

Net Link Up

An network link was available for the adapter.

13030

Net Link Down

The network link was removed from the adapter.

13031

Net Dup Address

The adapter uses the same IP address as another device on the network.

13032

Net Comm Fault

The adapter detected a communications fault on the network.

13033

Net Sent Reset

The adapter received a reset from the network.

13034

Net IO Close

An I/O connection from the network to the adapter was closed.

13035

Net Idle Fault

The adapter received “idle” packets from the network.

13036

Net IO Open

An I/O connection from the network to the adapter has been opened.

13037

Net IO Timeout

An I/O connection from the network to the adapter has timed out.

13038

Net IO Size Err

The adapter received an incorrectly sized I/O packet.

13039

PCCC IO Close

The device sending PCCC Control messages to the adapter has set the PCCC
Control Timeout to zero.

13040

PCCC IO Open

The adapter has begun receiving PCCC Control messages (the PCCC Control
Timeout was previously set to a non-zero value).