FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-36

Pn000.1 Control

Mode

9

Speed Control: When /P-CON (/C-SEL) is ON
Set the parameter Pn002.0 as shown below.

Parameter
Pn002.0
State

Speed Reference
Input (V-REF)
(CN1-5,6)

Torque Reference
Input (T-REF)
(CN1-9,10)

Comments

Speed Control

0

Speed Reference

Cannot be used.

Torque limit speed control by analog
voltage reference

1

Speed Reference

Torque Limit

See 5.2.9 Speed Feed-
Forward Function

for

more details on torque
limit speed control by
analog voltage
reference.

Speed control with torque feed-forward

2

Speed reference

Torque feed-
forward

See 5.2.8 Torque Feed-
Forward Function

for

more details on torque
feed-forward speed
control.

8 Position

Control

Ù

Torque Control

Can be used to switch between position control (pulse train reference) and torque
control.

/P-CON (/C-SEL)(CN1-41) is used to switch control.

CN1-41 State

Selects

Open Position

Control

0 V

Torque Control


6

Speed Control (Contact Reference) Ù

Torque Control

Can be used to switch between speed (contact reference) and torque control.

/P-CON (/C-SEL)(CN1-45) and /N-CL(SPD-B)(CN1-46) are used to switch control.

Parameter

/P-CL (/SPD-A)

CN1-45

State

Parameter

/N-CL (/SPD-B)

CN1-46

State

0 0

Torque

Control

0 1
1 1
1 0

Speed Control
(Contact reference)


Note:

Input signal /C-SEL can be used only when a signal is allocated to the input circuit. See

5.3.3 Input Circuit

Signal Allocation.