FSP Amplifier User’s Manual

Chapter 6: Servo Adjustment

6-7

6.2.6. Load Inertia Setting

In order to use values of Loop Gains that are closely related to the
characteristics of your system, loop gains are normalized in Hertz. This
normalization of parameters is done according to the assumed inertia of the
system.
You should do a rough estimation of the inertia of the load for your system
and input its value in the Load Inertia Ratio parameter (Pn103).
Set Pn103 to the following value.

Pn103 =

)

(J

Inertia

Rotor

Servomotor

)

(J

Inertia

Motor Load

M

L

x 100%

Parameter Signal

Setting

(%)

Application

Pn103 Inertia

Ratio

Range: 0 to 10000
Default Setting: 0

Speed, Torque,
Position Control, and
Programming


The following shows how to calculate the Load Inertial ratio for different
mechanical systems:















Estimation of Equivalent Load ( J

load

)

Case 1: Load is a cylinder directly mounted or coupled to the motor axis:

32

4

d

l

J

load

×

×

×

=

ρ

π

ρ is the density of the load material[kg/m

3

].

L is the length
D is the diameter of the load [m].

Case 2: Load is driven through a gear with ratio N:
Equivalent load on motor is:

2

N

J

J

load

=

Case 3: Load is a mass driven by a ball screw having pitch:

2

Pitch

M

load

J

×

=

+ J

screw

+ J

coupling

J

load

,

Æ Kg.m

2

, M

Æ Kg,

Pitch

Æ meter/radian

Other Cases: Make your own rough load inertia evaluations.