A.32: regenerative overload – Yaskawa FSP Amplifier User Manual
Page 276
Advertising
FSP Amplifier User’s Manual
Chapter 9: Inspection, Maintenance, and Troubleshooting
9-11
A.32: Regenerative Overload
Display and Outputs
Alarm Outputs
Alarm Code Output
ALO1 ALO2
ALO3
ALM Output
ON ON
OFF
OFF
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
A
During
servomotor operation
A
A,B
Cause of the Problem
Solution
A
Regenerative power exceeds the limit.
Use an external regenerative
resistor that matches the
regenerative power capacity.
B
Alarm occurs although an external
regenerative resistor is used and the
temperature rise of the regenerative
resistor is small.
Correct parameter Pn600.