FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-6

„

Servomotor Stop Mode for P-OT and N-OT Input Signals

Set the following parameters to specify the servomotor Stop mode when P-
OT and N-OT input signals are used.
Specify the servomotor Stop mode when either of the following signals is
input during servomotor operation.
• Forward run prohibited input (P-OT, CN1-42)
• Reverse run prohibited input (N-OT, CN1-43)

• Set the parameters according to limit switch type (NO or NC)

Parameter Signal

Setting

Description

Example: 2

Uses the P-OT input signal to prevent
forward rotation. (Forward rotation is
prohibited when CN1-42 is open and is
allowed when CN1-42 is at 0 V).

Default Setting: 8

Does not use the P-OT input signal to
prevent forward rotation. (Forward
rotation is always allowed and has the
same effect as shorting CN1-42 to 0 V).

Pn50A.3

P-OT Signal
Mapping
(Forward Run
Prohibit Input
Signal)

Example: B

Inputs the reverse signal from CN1-42
input terminal.

For more options of parameters Pn50A.3 and Pn50B.0 refer to Appendix D.3. Input Signal
Selections

Example: 3

Uses the N-OT input signal to prevent
reverse rotation. (Reverse rotation is
prohibited when CN1-43 is open and is
allowed when CN1-43 is at 0 V).

Default Setting: 8

Does not use the N-OT input signal to
prevent reverse rotation. (Reverse
rotation is always allowed and has the
same effect as shorting CN1-43 to 0 V).

Pn50B.0

N-OT Signal
Mapping
(Reverse Run
Prohibit Input
Signal)

Example: C

Inputs the reverse signal from CN1-43
input terminal.


Connection example:

Normally Closed type




P-OT

N-OT

COM of 24 V




FSP Amplifier


CN1-42



CN1-43