Chapter 9: Inspection, Maintenance, and Troubleshooting

9-19

„

A.7A: Heat Sink Overheated

Heat sink temperature exceeds 100°C.

Display and Outputs

Alarm Outputs

Alarm Code Output

ALO1 ALO2

ALO3

ALM Output

ON ON

ON

OFF

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

During servomotor
operation.

W hen control
power is turned
ON.

A, B
C, D

E

Cause of the Problem

Solution

A

The ambient temperature of the servo
amplifier exceeds 55°C.

Alter conditions so that the
ambient temperature goes below
55°C.

B

Inadequate airflow around the heat
sink.

Provide sufficient space as
specified.

C

Fan stopped.

Replace servo amplifier.

D

Servo amplifier is operating under
overload.

Reduce load.

E

Defective servo amplifier.

Replace servo amplifier.

Note: Larger servo amplifiers (1.5 kW., or larger) will display alarm A.10 if the heat sink overheats.