FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-44

5.2.10. Reference Pulse Inhibit Function (/INHIBIT)

This function inhibits the servo amplifier from counting input reference
pulses during position control. The servomotor remains locked (clamped)
while the function is in use. The /P-CON(/INHIBIT) signal is used to
enable or disable the function.

Reference

Pn000.1

XtraDrive

pulse

/ P-CON
(/ INHIBIT)

/ P-CON(/ INHIBIT)

1

B

+

_

Feedback pulse

Error
counter

FSP Amplifier

„

Using Reference Pulse Inhibit Function (/INHIBIT)

To use the inhibit function, set the parameter as shown below to "C".

Parameter Signal

Setting Control

Mode

Pn000.1

Control Method
Selection

Default Setting: D

Speed, Torque,
Position Control,
and Programming


The following settings enable the inhibit function.

Pn000.1

Setting

Description

C

Enables the inhibit function. Always counts reference pulses.

Enables the inhibit function. The /P-CON (/INHIBIT) signal is used to enable or
disable the inhibit function.

/P-CON (/INHIBIT)

Description

OFF

Counts reference pulses.

B

ON

Prohibits the servo amplifier from counting
reference pulses.
The servomotor remains locked.

Note:

Parentheses ( ) around an /INHIBIT signal indicate that a signal has been allocated to the input circuit.
See

5.3.3 Input Circuit Signal Allocation for more details.