The following warning codes are output in 3 bits – Yaskawa FSP Amplifier User Manual

Page 137

Advertising
background image

FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-70

Parameter Signal

Setting

Control

Mode

Pn50F

Output Signal Selections 2

Default Setting: 0000

Speed, Torque,
Position Control, and
Programming


Pn50F.3 is used to allocate the /WARN output signals above.

Output Terminal (CN1-)

Pn50F.3 State

*1 *2

0 —

1 25 26

2 27 28

3 29 30

Note:

*1 and *2 are output terminals allocated with parameter Pn 510.0.
Multiple signals allocated to the same output terminal follow Boolean OR logic. In order to use the /WARN
output signal alone, set other output signals to a value other than the one allocated to the /WARN signal. See
5.3.4 Output Circuit Signal Allocation.

/WARN

Warning

output signal

SO1 (CN1-25, 26)

SO2 (CN1-27, 28)

SO3 (CN1-29, 30)

Pn50F.3

1

2

3

Output terminals

The following parameter is used to output warning details with an alarm
code.

Parameter Signal

Setting

Control

Mode

Pn001.3

Warning Code Output
Selection

Default Setting: 0

Speed, Torque,
Position Control,
and Programming

Pn001.3 Setting

Result

0

Outputs alarm codes only for alarm codes ALO1,
ALO2 and ALO3.

1

Outputs both alarm and warning codes for alarm
codes ALO1, ALO2 and ALO3 and outputs an
alarm code when an alarm occurs.


The following warning codes are output in 3 bits.

Warning Code Output

Warning

Indication

ALO1 ALO2 ALO3

Warning Description

A.91

ON signal

(low level)

OFF signal
(high level)

OFF signal
(high level)

Overload

A.92

OFF signal
(high level)

ON signal

(low level)

OFF signal
(high level)

Regenerative overload